Thermocouples<br />

with direct<br />

looping-in of<br />

compensation box<br />

Equaalizing conductor<br />

(material with same<br />

thermal e.m.f.<br />

as thermocouple)<br />

Thermocouple<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

.<br />

.<br />

.<br />

When all thermocouples are wired floating, it is possible to loop the<br />

compensation box directly into the measuring circuit.<br />

The compensation channel CH7 which is not required can now be used as an<br />

additional measurement input.<br />

The measurement mode ”thermocouples with linearization and<br />

compensation to 0 o C” must be set for all channels. The thermocouples<br />

which use a compensation box must all be of the same type.<br />

Supply<br />

conductor<br />

(copper)<br />

Reference junction<br />

<br />

.<br />

.<br />

.<br />

+<br />

-<br />

CH0<br />

.<br />

.<br />

.<br />

CH6<br />

CH7<br />

U v<br />

M+<br />

M-<br />

M+<br />

M-<br />

M+<br />

M-<br />

ADU<br />

Compensation box with<br />

reference junction temperature of 0<br />

o C<br />

SIMATIC S7 Ex Analog Modules<br />

P5V<br />

M<br />

Logic<br />

Backplane<br />

bus<br />

Fig. 3-5 Connection of floating thermocouples to a compensation box and measurement mode ”Compensation to<br />

0 o C” with the analog input module SM 331; AI 8 x TC/4 x RTD<br />

Advantages: – When using a compensation box with a reference junction temperature of 0 oC, the<br />

voltage corresponding to the reference junction temperature is subtracted directly.<br />

– Channel 7 can be used as an additional measuring channel in this circuit variant.<br />

– The number of connection lines between the compensation box and analog input<br />

module is reduced.<br />

– Faults which are attributed to isolated compensation measurement do not occur.<br />

Condition: The thermocouples which are routed to the same compensation box must only be<br />

grounded once at one point.<br />

3-29