Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The selected type of housing is characterized by the fact that it is able to<br />

withstand explosions occurring inside the housing and that an explosive<br />

gas/air mixture surrounding the housing is not ignited. In addition, the<br />

surface temperature does not exceed the limit values of the temperature<br />

classes. Cable glands that are protected against transmission of internal<br />

ignition and isolated against the housing wall must be used for routing the<br />

supply leads into the flameproof housing.<br />

A housing with ”increased safety” is used as a terminal compartment. Special<br />

screwed glands are used for the cable entries.<br />

The housing must be certified by a testing authority to comply with the EEx<br />

d type of protection and the relevant design requirements.<br />

Explosion protection of the housing: EEx de <strong>II</strong> T5 .. T6.<br />

The cables must comply with the DIN EN 50014 and DIN EN 50 020<br />

standards for intrinsically safe circuits or with DIN EN 50039 for circuits<br />

with ”increased safety”.<br />

The cables for the assembly are to be installed in such a way that they are<br />

endangered neither by thermal, mechanical nor chemical load or stress.<br />

Note<br />

The cables should be installed in cable conduits if necessary.<br />

The terminal connectors for the power supply cable and the bus line should<br />

always meet the requirements of the ”increased safety” tape of protection.<br />

The claming points of the intrinsically safe circuits should always be<br />

implemented according to the guidelines of ”Intrinsic safety”.<br />

The assembly is connected to a 24 V DC supply circuit fed by a power<br />

supply unit with safe electrical isolation. The supply circuit must be<br />

protected by an appropriate circuit-breaker. This circuit-breaker is installed<br />

outside the Ex zone.<br />

The switch for enabling the system should comply with ”EEx de <strong>II</strong> T6” type<br />

of protection.<br />