Current measuring<br />

ranges<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 3-4 shows the representation of the digitized measured value for the<br />

current measuring ranges 0 to 20 mA and 4 to 20 mA.<br />

Table 3-4 Representation of the digitized measured value of analog input module SM 331; AI 4 x 0/4...20 mA<br />

and AI 2 x 0/4...20 mA HART<br />

Measuring<br />

range g<br />

from<br />

0 to 20 mA<br />

Measuring<br />

range g<br />

from<br />

4 to 20 mA<br />

Units<br />

decimal hexadecimal<br />

Range<br />

> 23.515 >.22.810 32767 7FFFH Overflow<br />

23.515 22.810 32511 7EFFH<br />

: : : : Overrange g<br />

20.0007 20.0005 27649 6C01H<br />

20.000 20.000 27648 6C00H<br />

14.998 16.000 20736 5100H<br />

: : : :<br />

0.0 4.000 0 0H<br />