Faults and<br />

corrective<br />

measures<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 3-27 provides a list of possible causes and corresponding corrective<br />

measures for individual diagnostic messages.<br />

Bear in mind that, in order to detect faults which are indicated by means of<br />

configurable diagnostic messages, the module must also be parameterized<br />

accordingly.<br />

Table 3-27 Diagnostic messages of analog output module SM 332; AO 4 x 0/4...20 mA and their possible causes<br />

and corrective measures<br />

Wire break<br />

Diagnostic message Possible fault cause Corrective measures<br />

Break in line between module and<br />

actuator<br />

Incorrect parameters in module Module supplied with invalid<br />

parameters<br />

Connect line<br />

Voltage at load resistor > 12V Lower load resistance to 500 <br />

Channel not connected (open) Deactivate channel (”Measurement<br />

mode parameter)<br />

Check parameterization of module<br />

and re-load valid parameters<br />

Module not parameterized Module not supplied with parameters Include module in parameterization<br />

No external auxiliary voltage No module supply voltage L+ Provide L+ supply<br />

No internal auxiliary voltage No module supply voltage L+ Provide L+ supply<br />

Module-internal fuse defective Replace module<br />

Fuse blown Module-internal fuse defective Replace module<br />

Time watchdog tripped In part, high electromagnetic<br />

interference<br />

EPROM error<br />

CPU error<br />

RAM error<br />

Reading out<br />

diagnostic<br />

messages<br />

Eliminate interference sources<br />

Module defective Replace module<br />

In part, high electromagnetic<br />

interference<br />

Module defective Replace module<br />

SIMATIC S7 Ex Analog Modules<br />

Eliminate interference sources and<br />

switch CPU supply voltage OFF/ON<br />

You can read out the detailed diagnostic messages in STEP 7 after setting<br />

diagnostics for the analog modules (refer to /231/).<br />

3-49