Influence of<br />

supply voltage and<br />

operating status<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The input values of the SM 321; DI 4 x NAMUR are dependent on the supply<br />

voltages and operating status of the CPU.<br />

Table 2-7 provides an overview of these dependencies.<br />

Table 2-7 Dependencies of the input values for CPU operating status and supply<br />

voltage L+ of SM 321; DI 4 x NAMUR<br />

Operating status<br />

CPU<br />

Supply voltage L+ at<br />

digital module<br />

Input value of digital<br />

module<br />

POWER ON RUN L+ applied Process value<br />

L+ not applied 0-signal<br />

STOP L+ applied Process value<br />

L+ not applied 0-signal<br />

POWER OFF - L+ applied -<br />

SIMATIC S7 Ex Digital Modules<br />

L+ not applied -<br />

Failure of the supply voltage L+ of the SM 321; DI 4 x NAMUR is always<br />

indicated by the SF-LED on the front of the module and additionally entered<br />

in diagnostics.<br />

In the event of the module supply voltage L+ failing, the input value is<br />

initially held for 20 to 40 ms before the ”0” signal is transferred to the CPU.<br />

Dips in the supply voltage of < 20 ms do not change the process value, but<br />

they trigger a diagnostic interrupt and the group error LED is lit.<br />