SIMATIC S7 Ex Analog Modules<br />

Thermocouples<br />

with compensation<br />

box<br />

3-28<br />

Equalizing conductor<br />

(same material as<br />

thermocouple)<br />

Thermocouple<br />

UISO: Difference in potential between channels and M- terminal of<br />

CPU<br />

UCM: Differences in potential between channels<br />

Necessary when all thermocouples which are connected to the inputs of a<br />

module and which have the same reference junction compensate as follows.<br />

The thermocouples which use a compensation box must be of the same type.<br />

Each of the thermocouples can be grounded at any arbitrary point.<br />

Supply<br />

conductor<br />

(copper)<br />

Reference junction<br />

<br />

+<br />

-<br />

U v<br />

CH0<br />

.<br />

.<br />

.<br />

CH6<br />

CH7<br />

M+<br />

M-<br />

M+<br />

M-<br />

M+<br />

M-<br />

ADU<br />

Compensation box with<br />

reference junction temperature of 0 o C<br />

P5V<br />

M<br />

Logic<br />

Backplane<br />

bus<br />

Fig. 3-4 Connection of thermocouples with external compensation box to the isolated analog input module SM<br />

331; AI 8 x TC/4 x RTD<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04