SIMATIC S7 Ex Digital Modules<br />

Channel groups<br />

allocation<br />

Parameters of the<br />

digital output<br />

module<br />

2-20<br />

Table 2-9 shows the allocation of the 4 channels to the 4 channel groups of<br />

digital output.<br />

Table 2-9 Allocation of the 4 channels to the 4 channel groups of<br />

SM 322; DO 4 x 24V/10mA and SM 322; DO 4 x 15V/20mA<br />

Channel Allocated channel group<br />

Channel 0 Channel group 0<br />

Channel 1 Channel group 1<br />

Channel 2 Channel group 2<br />

Channel 3 Channel group 3<br />

Table 2-10 provides an overview of the parameters and shows what<br />

parameters:<br />

are static or dynamic,<br />

can be used for the module as a whole or for a channel group.<br />

Table 2-10 Parameter of SM 322; DO 4 x 24V/10mA and SM 322; DO 4 x 15V/20mA<br />

Parameter SM 322; DO 4 x 24 V DC/10mA or SM 322; DO 4 x 15V/20mA<br />

Value range Default Type Effective range<br />

Basic settings<br />

Diagnostic interrupt enable yes/no<br />

no<br />

dynamic Module<br />

Retain last value<br />

yes/no<br />

no<br />

dynamic Module<br />

Switch to substitute value yes/no<br />

yes<br />

dynamic Module<br />

Substitute value<br />

0 / 1<br />

0<br />

dynamic Module<br />

Diagnostics<br />

Short to chassis ground<br />

Wire break 1)<br />

yes/no<br />

no<br />

static<br />

Channel group<br />

yes/no<br />

no<br />

static<br />

Channel group<br />

Supply voltage fault yes/no<br />

no<br />

static<br />

Channel group<br />

1) If wire break diagnostic enable is not parameterized, there will be no indication by the channel fault LED in the event<br />

of wire break.<br />

Diagnostics<br />

Parameterizing<br />

diagnostics<br />

You can use the diagnostic function to determine whether signal output takes<br />

place without errors.<br />

The diagnostics is parameterized with STEP 7.<br />

I/O Modules with Intrinsically-Safe Signals<br />