I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Fig. 3-11 shows the connection of current sensors as 2-wire transducers to the<br />

analog input module SM 331; AI 4 x 0/4...20 mA and AI 2 x 0/4...20 mA<br />

HART.<br />

, , <br />

MU<br />

e.g.<br />

pressure,<br />

temperature<br />

L+<br />

M<br />

I<br />

4...20 mA<br />

U M<br />

L 0+<br />

M 0+<br />

M 0-<br />

RS 50<br />

Transducer supply<br />

A<br />

D<br />

Logic<br />

Backplane<br />

bus<br />

Fig. 3-11 Connection of 2-wire transducers to the analog input module SM 331; AI<br />

4 x 0/4...20 mA and AI 2 x 0/4...20 mA HART.<br />

Fig. 3-12 shows the connection of current sensors as 4-wire transducers with<br />

external transducer supply to the analog input module SM 331;<br />

AI 4 x 0/4...20 mA and AI 2 x 0/4...20 mA HART.<br />

, , <br />

MU<br />

e.g.<br />

pressure,<br />

temperature<br />

U v +<br />

U v -<br />

L+<br />

M<br />

0/4...20 mA<br />

U M<br />

L 0+<br />

M 0+<br />

M 0-<br />

RS 50<br />

SIMATIC S7 Ex Analog Modules<br />

Transducer supply<br />

A<br />

D<br />

Logic<br />

Backplane<br />

bus<br />

Fig. 3-12 Connection of 4-wire transducers with external supply to the analog input<br />

module SM 331; AI 4 x 0/4...20 mA and AI 2 x 0/4...20 mA HART.<br />

3-35