22.07.2013 Views

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SIMATIC S7 HART Analog Modules<br />

Interference suppression, error limits<br />

Crosstalk attenuation between<br />

outputs<br />

Operational limit (in total<br />

temperature range, referred to<br />

output range)<br />

Basic error limit (operational<br />

limit at 25C, referred to output<br />

range)<br />

Temperature error (referred to<br />

output range)<br />

Linearity error (referred to<br />

output range)<br />

Repeatability in steady-state<br />

condition at bei 25C, referred<br />

to output range)<br />

Output ripple; range 0 to 50 kHz<br />

(referred to output range)<br />

Interrupts,diagnostics<br />

4-24<br />

130 dB<br />

0.55 %<br />

0.15 %<br />

0.01 %/K<br />

0.03 %<br />

0.005 %<br />

0.02 %<br />

Interrupts<br />

Diagnostic interrupt configurable<br />

Diagnostic functions configurable<br />

Group fault indication red LED (SF)<br />

Channel fault indication red LED (F) per<br />

channnel<br />

Diagnostic information<br />

readout<br />

possible<br />

Monitoring for<br />

Wire break yes<br />

from output value<br />

> 0.5 mA<br />

HART communication active<br />

and OK<br />

green LED (H)<br />

Safety data (see Certificate of Conformity in<br />

Appendix A)<br />

Type of protection to EN 50020 [EEx ib] <strong>II</strong>C<br />

Maximum values of the output<br />

circuits (per channel)<br />

U0 (no-load output<br />

voltage)<br />

max. 19 V<br />

I0 (short-circuit current) max. 66 mA<br />

P0 (load power) max. 506 mW<br />

L0 (permissible external<br />

inductance)<br />

max. 7.5 m<br />

C0 (permissible external<br />

capacitance)<br />

max. 230 nF<br />

Um (error voltage) max. 60V DC<br />

Ta (permissible ambient<br />

temperature)<br />

max. 60C<br />

Data for sensor selection<br />

Output ranges (rated values)<br />

Current from 0 to 20 mA<br />

from 4 to 20 mA<br />

Load impedance (in rated range<br />

of output)<br />

for current outputs<br />

– resistive load<br />

– inductive load<br />

– capacitive load<br />

1) Limitation by KEMA approval<br />

When used in a non-Ex area can be controlled as an:<br />

– inductive load max. 15 mH<br />

– capacitive load max. 3 μF *) can be set as the load impedance.<br />

*) however, HART communication no longer possible<br />

max. 650 <br />

max. 7.5 mH 1)<br />

max. 230 nF 1)<br />

Current output<br />

No-load voltage max. 19 V<br />

Destruction limit for externally<br />

applied voltages / currents<br />

Voltages<br />

max. + 17 V / - 0.5V<br />

Current<br />

max. + 60 mA / - 1A<br />

Connection of actuators<br />

for current output<br />

2-wire connection yes<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!