II - DCE FEL ČVUT v Praze
II - DCE FEL ČVUT v Praze
II - DCE FEL ČVUT v Praze
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SIMATIC S7 Ex Analog Modules<br />
Analog Output SM 332; AO 4 x 0/4...20 mA<br />
Dimensions and Weight<br />
Dimensions W x H x D (mm) 40 x 125 x 120<br />
Weight<br />
Module-specific data<br />
approx. 280 g<br />
Number of outputs 4<br />
Line length, shielded max. 200 m<br />
Type of protection PTB [EEx ib] <strong>II</strong>C<br />
(see Appendix A)<br />
to EN 50020<br />
Test number Ex-96.D.2026 X<br />
Type of protection FM CL I, DIV 2,<br />
(see Appendix B)<br />
Voltages, currents, potentials<br />
GP A, B, C, D T4<br />
Bus power supply<br />
5 V DC<br />
Rated load voltage L+ 24 V DC<br />
Reverse voltage protection yes<br />
Isolation<br />
Between channels and<br />
backplane bus<br />
yes<br />
Between channels and load<br />
voltage L+<br />
yes<br />
between channels yes<br />
Between backplane bus<br />
and load voltage L+<br />
yes<br />
Permissible difference in potential (UISO) of signals<br />
from hazardous area<br />
Between channels and 60 V DC<br />
backplane bus<br />
30 V AC<br />
Between channels and load 60 V DC<br />
voltage L+<br />
30 V AC<br />
between channels 60 V DC<br />
30 V AC<br />
Between backplane bus 60 V DC<br />
and load voltage L+ 30 V AC<br />
3-72<br />
Voltages, currents, potentials continued<br />
Permissible difference in potential (UISO) for signals<br />
from non-hazardous area<br />
between channels and<br />
backplane bus<br />
Between channels and load<br />
voltage L+<br />
400 V DC<br />
250 V AC<br />
400 V DC<br />
250 V AC<br />
Between channels 400 V DC<br />
250 V AC<br />
Between backplane bus<br />
and load voltage L+<br />
Insulation tested<br />
Channels with respect to<br />
backplane bus and load<br />
voltage L+<br />
Channels among each<br />
other<br />
Backplane bus with respect<br />
to load voltage L+<br />
Current input<br />
from backplane bus<br />
From load voltage L+<br />
(at rated data)<br />
75 V DC<br />
60 V AC<br />
with 1500 V AC<br />
with 1500 V AC<br />
with 500 V DC<br />
max. 80 mA<br />
max. 180 mA<br />
Module power loss typical 4 W<br />
Analog value formation<br />
Resolution (incl. overrange) 15 Bit<br />
Cycle time (all channels)<br />
Transient recovery time<br />
9.5 ms<br />
for resistive load 0.2 ms<br />
for capacitive load 0.5 ms<br />
for inductive load 0.2 ms<br />
Substitute values switchable yes, configurable<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04