22.07.2013 Views

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SIMATIC S7 Ex Analog Modules<br />

Analog Output SM 332; AO 4 x 0/4...20 mA<br />

Dimensions and Weight<br />

Dimensions W x H x D (mm) 40 x 125 x 120<br />

Weight<br />

Module-specific data<br />

approx. 280 g<br />

Number of outputs 4<br />

Line length, shielded max. 200 m<br />

Type of protection PTB [EEx ib] <strong>II</strong>C<br />

(see Appendix A)<br />

to EN 50020<br />

Test number Ex-96.D.2026 X<br />

Type of protection FM CL I, DIV 2,<br />

(see Appendix B)<br />

Voltages, currents, potentials<br />

GP A, B, C, D T4<br />

Bus power supply<br />

5 V DC<br />

Rated load voltage L+ 24 V DC<br />

Reverse voltage protection yes<br />

Isolation<br />

Between channels and<br />

backplane bus<br />

yes<br />

Between channels and load<br />

voltage L+<br />

yes<br />

between channels yes<br />

Between backplane bus<br />

and load voltage L+<br />

yes<br />

Permissible difference in potential (UISO) of signals<br />

from hazardous area<br />

Between channels and 60 V DC<br />

backplane bus<br />

30 V AC<br />

Between channels and load 60 V DC<br />

voltage L+<br />

30 V AC<br />

between channels 60 V DC<br />

30 V AC<br />

Between backplane bus 60 V DC<br />

and load voltage L+ 30 V AC<br />

3-72<br />

Voltages, currents, potentials continued<br />

Permissible difference in potential (UISO) for signals<br />

from non-hazardous area<br />

between channels and<br />

backplane bus<br />

Between channels and load<br />

voltage L+<br />

400 V DC<br />

250 V AC<br />

400 V DC<br />

250 V AC<br />

Between channels 400 V DC<br />

250 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

Insulation tested<br />

Channels with respect to<br />

backplane bus and load<br />

voltage L+<br />

Channels among each<br />

other<br />

Backplane bus with respect<br />

to load voltage L+<br />

Current input<br />

from backplane bus<br />

From load voltage L+<br />

(at rated data)<br />

75 V DC<br />

60 V AC<br />

with 1500 V AC<br />

with 1500 V AC<br />

with 500 V DC<br />

max. 80 mA<br />

max. 180 mA<br />

Module power loss typical 4 W<br />

Analog value formation<br />

Resolution (incl. overrange) 15 Bit<br />

Cycle time (all channels)<br />

Transient recovery time<br />

9.5 ms<br />

for resistive load 0.2 ms<br />

for capacitive load 0.5 ms<br />

for inductive load 0.2 ms<br />

Substitute values switchable yes, configurable<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04