Wiring diagram<br />

SM 33 1<br />

AI 8 xTC / 4 x RTD<br />

+ input 0/0<br />

- input 0/0<br />

+ input 1/-<br />

- input 1/-<br />

+ input 2/2<br />

- input 2/2<br />

+ input 3/-<br />

- input 3/-<br />

+ input 4/4<br />

- input 4/4<br />

+ input 5/-<br />

- input 5/-<br />

+ input 6/6<br />

- input 6/6<br />

+ input 7/-<br />

- input 7/-<br />

X 2<br />

3 4<br />

331-7SF00-0AB0<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

x<br />

SF<br />

F0<br />

F1<br />

F2<br />

F3<br />

[EEx ib] <strong>II</strong>C<br />

F4<br />

F5<br />

F6<br />

F7<br />

Fig. 3-16 shows the module view and the terminal diagram of the SM 331;<br />

AI 8 x TC/4 x RTD<br />

You will find detailed technical specifications of the analog input module<br />

SM 331; AI 8 x TC/4 x RTD on the following pages.<br />

5V internal<br />

M internal<br />

Isolation<br />

Logic and<br />

backplane bus<br />

interfacing<br />

Isolation<br />

SF<br />

Internal<br />

supply<br />

Internal<br />

compensation<br />

F (0...7)<br />

ADU<br />

Power<br />

source<br />

SF group fault indication [red]<br />

Channel-specific fault indication [red]<br />

F (0...7) [TC], F (0,2,4,6) [RTD]<br />

Optomultiplexer<br />

Fig. 3-16 Module view and block diagram of SM 331; AI 8 x TC/4 x RTD<br />

Notes on<br />

intrinsically-safe<br />

installation<br />

SIMATIC S7 Ex Analog Modules<br />

Thermocouples, voltage<br />

measurement<br />

M0 +<br />

M0 CH0<br />

M1 +<br />

M1 CH1<br />

M2 +<br />

M2 CH2<br />

M3 +<br />

M3 CH3<br />

M 4 +<br />

M4 M5 +<br />

M5 M6 +<br />

M6 <br />

M7 +<br />

M7 Resistance<br />

measurement<br />

CH4<br />

CH5<br />

CH6<br />

CH7<br />

M 0 +<br />

M0 IC0 +<br />

IC0 M1 +<br />

M1 IC1 +<br />

IC1 M 2 +<br />

M2 IC2 +<br />

IC2 M3 +<br />

M3 IC3 +<br />

IC3 CH0<br />

CH2<br />

CH4<br />

CH6<br />

You must connect the DM 370 dummy module between the CPU or IM 153-2<br />

(in a distributed configuration) and the Ex I/O modules whose signal cables<br />

lead into the hazardous location. In a distributed configuration with an active<br />

backplane bus, you should use the ex dividing panel/ ex barrier instead of the<br />

dummy module. Additional information on system design can be found in<br />

Sections 1.3 - 1.5.<br />

3-55