Analog value formation<br />

Measuring principle SIGMA-DELTA<br />

Integration time/conversion<br />

time/resolution (per<br />

channel)<br />

configurable<br />

Integration time in ms<br />

Basic conversion time<br />

incl. integration time in<br />

ms (several channels<br />

enabled)<br />

Basic conversion time<br />

incl. integration time in<br />

ms (one channel<br />

enabled)<br />

Resolution in bit + sign<br />

(incl. overrange)<br />

Interference voltage<br />

rejection for interference<br />

frequency f1 in Hz<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

yes yes<br />

2.5 162 yes yes<br />

/3 20 100<br />

7.5 50 60 300<br />

2.5 16 2 /3 20 100<br />

10+<br />

sign<br />

Interfere nce rejection, error limits<br />

13+<br />

sign<br />

13+<br />

sign<br />

15+<br />

sign<br />

400 60 50 10<br />

Interference voltage rejection for f = n x (f1 1 %),<br />

(f1 = interference frequency)<br />

Common-mode<br />

interference channels with<br />

respect to M-terminal of<br />

CPU (UISO < 60 V)<br />

> 130 dB<br />

Normal-mode interference<br />

(measured value +<br />

interference must be<br />

within the input range<br />

0 to 22 mA)<br />

> 60 dB<br />

Crosstalk attenuation between<br />

inputs (UISO < 60 V)<br />

> 130 dB<br />

Operational limit (in total temperature range, referred to<br />

input range)<br />

from 0/4 to 20 mA 0.45 %<br />

Basic error (operational limit at 25 C, referred to input<br />

range)<br />

from 0/4 to 20 mA 0.1 %<br />

Temperature error<br />

(referred to input range)<br />

Linearity error<br />

(referred to input range)<br />

Repeatability (in steady-state<br />

condition at 25 C, referred to<br />

input range)<br />

0.01%/K<br />

0.01 %<br />

0.05 %<br />

Interference rejection, error limits continued<br />

Influence of a HART signal superimposed on the input<br />

signal referred to the input range<br />

Error at integration time<br />

2.5 ms 0.25%<br />

162 /3 ms 0.05%<br />

20 ms 0.04%<br />

100 ms 0.02%<br />

Interrupts, Diagnostics<br />

SIMATIC S7 Ex Analog Modules<br />

Interrupts<br />

Limit interrupt Configurable<br />

channels 0 and 2<br />

Diagnostic interrupt configurable<br />

Diagnostic functions configurable<br />

Group fault indication red LED (SF)<br />

Channel fault indication red LED (F)<br />

per channel<br />

Diagnostic information<br />

readout<br />

possible<br />

Characteristic data for transducer supply<br />

No-load voltage < 25.2 V<br />

Output voltage for<br />

transducer and line at<br />

22 mA transducer current<br />

(50 measuring shunt<br />

incorporated in module)<br />

> 13 V<br />

Data for sensor selection<br />

Input ranges (rated values) /<br />

input resistance<br />

Current 0 to 20 mA;<br />

4 to 20 mA:<br />

Permissible input current for<br />

current input (destruction<br />

limit)<br />

Signal generator connection<br />

40 mA<br />

for current measurement<br />

as 2-wire transducer possible<br />

as 4-wire transducer possible<br />

/50 Ω<br />

/50 Ω<br />

3-67