Analog value formation<br />
Measuring principle SIGMA-DELTA<br />
Integration time/conversion<br />
time/resolution (per<br />
channel)<br />
configurable<br />
Integration time in ms<br />
Basic conversion time<br />
incl. integration time in<br />
ms (several channels<br />
enabled)<br />
Basic conversion time<br />
incl. integration time in<br />
ms (one channel<br />
enabled)<br />
Resolution in bit + sign<br />
(incl. overrange)<br />
Interference voltage<br />
rejection for interference<br />
frequency f1 in Hz<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04<br />
yes yes<br />
2.5 162 yes yes<br />
/3 20 100<br />
7.5 50 60 300<br />
2.5 16 2 /3 20 100<br />
10+<br />
sign<br />
Interfere nce rejection, error limits<br />
13+<br />
sign<br />
13+<br />
sign<br />
15+<br />
sign<br />
400 60 50 10<br />
Interference voltage rejection for f = n x (f1 1 %),<br />
(f1 = interference frequency)<br />
Common-mode<br />
interference channels with<br />
respect to M-terminal of<br />
CPU (UISO < 60 V)<br />
> 130 dB<br />
Normal-mode interference<br />
(measured value +<br />
interference must be<br />
within the input range<br />
0 to 22 mA)<br />
> 60 dB<br />
Crosstalk attenuation between<br />
inputs (UISO < 60 V)<br />
> 130 dB<br />
Operational limit (in total temperature range, referred to<br />
input range)<br />
from 0/4 to 20 mA 0.45 %<br />
Basic error (operational limit at 25 C, referred to input<br />
range)<br />
from 0/4 to 20 mA 0.1 %<br />
Temperature error<br />
(referred to input range)<br />
Linearity error<br />
(referred to input range)<br />
Repeatability (in steady-state<br />
condition at 25 C, referred to<br />
input range)<br />
0.01%/K<br />
0.01 %<br />
0.05 %<br />
Interference rejection, error limits continued<br />
Influence of a HART signal superimposed on the input<br />
signal referred to the input range<br />
Error at integration time<br />
2.5 ms 0.25%<br />
162 /3 ms 0.05%<br />
20 ms 0.04%<br />
100 ms 0.02%<br />
Interrupts, Diagnostics<br />
SIMATIC S7 Ex Analog Modules<br />
Interrupts<br />
Limit interrupt Configurable<br />
channels 0 and 2<br />
Diagnostic interrupt configurable<br />
Diagnostic functions configurable<br />
Group fault indication red LED (SF)<br />
Channel fault indication red LED (F)<br />
per channel<br />
Diagnostic information<br />
readout<br />
possible<br />
Characteristic data for transducer supply<br />
No-load voltage < 25.2 V<br />
Output voltage for<br />
transducer and line at<br />
22 mA transducer current<br />
(50 measuring shunt<br />
incorporated in module)<br />
> 13 V<br />
Data for sensor selection<br />
Input ranges (rated values) /<br />
input resistance<br />
Current 0 to 20 mA;<br />
4 to 20 mA:<br />
Permissible input current for<br />
current input (destruction<br />
limit)<br />
Signal generator connection<br />
40 mA<br />
for current measurement<br />
as 2-wire transducer possible<br />
as 4-wire transducer possible<br />
/50 Ω<br />
/50 Ω<br />
3-67