22.07.2013 Views

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SIMATIC S7 HART Analog Modules<br />

4.8.2 Diagnostic Data Records<br />

Structure and<br />

contents of the<br />

diagnostic data<br />

4-28<br />

The diagnostic data for a module can be up to 16 bytes long and consist of<br />

data records 0 and 1:<br />

Data record 0 contains system specific diagnostic data for the whole module:<br />

4 bytes. It is set on a system-wide basis and applies for both HART<br />

analog input and output.<br />

Data record 1 contains<br />

– 4 bytes of diagnostic data for an S7-300 which are also in data record<br />

0 and<br />

– Up to 12 bytes of module-class specific diagnostic data.<br />

Byte 0<br />

Byte 1<br />

Byte 2<br />

Byte 3<br />

7 6 5 4 3 2 1 0<br />

0<br />

Module fault<br />

Error (internal)<br />

Error (external)<br />

Channel error occurred<br />

External auxiliary voltage missing<br />

Parameters missing<br />

(set immediately after voltage recovery)<br />

Incorrect parameters in the module<br />

7 6 5 4 3 2 1 0<br />

0 0 0 1 1 0 0<br />

Module class CP<br />

Channel information available<br />

7 6 5 4 3 2 1 0<br />

0 0 0 0 0 0<br />

Cycle-time monitoring for the module<br />

responded (watchdog)<br />

Module-internal supply voltage failure<br />

7 6 5 4 3 2 1 0<br />

0 0<br />

Processor failure<br />

EPROM error<br />

RAM error<br />

ADC/DAC error<br />

Fuse blown<br />

Hardware interrupt lost (only with AI HART)<br />

Fig. 4-12 Diagnostic data: data record 0<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04