SIMATIC S7 Ex Analog Modules<br />

Temperature<br />

range, climatic,<br />

Ni 100<br />

3-10<br />

Table 3-9 shows the representation of the digitized measured value for the<br />

climatic temperature range of the sensor Ni 100 in accordance with<br />

DIN 43760.<br />

The same value range as in the standard range of the Ni 100 sensor applies in<br />

the climatic range Ni 100 only with a higher resolution of 0.01C instead of<br />

0.1 C.<br />

Table 3-9 Representation of the digitized measured value of an analog input<br />

module (temperature range, climatic, Ni 100)<br />

Temperature range,<br />

climatic<br />

Ni 100<br />

in C<br />

Decimal Hexadecimal Range<br />

> 295.00 32767 7FFFH Overflow<br />

295.00<br />

:<br />

250.01<br />

250.00<br />

:<br />

-60.00<br />

-60.01<br />

:<br />

-105.00<br />

29500<br />

:<br />

25001<br />

25000<br />

:<br />

-6000<br />

-6001<br />

:<br />

-10500<br />

733CH<br />

:<br />

61A9H<br />

61A8H<br />

:<br />

E890H<br />

E88FH<br />

:<br />

D6FCH<br />

Overrange 1)<br />

Rated range<br />

Underrange 1)<br />

< - 105.00 -32768 8000H Underflow<br />

1) The characteristic of the Ni 100 sensor is not defined in the overrange and<br />

underrange. The rise of the characteristic curve is retained on leaving the linearized<br />

rated range. It is not possible to specify the accuracy of these ranges.<br />