Temperature<br />

range, standard,<br />

Ni 100<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 3-8 shows the representation of the digitized measured value for the<br />

standard temperature range of the sensor Ni 100 in accordance with<br />

DIN 43760.<br />

Table 3-8 Representation of the digitized measured value of an analog input<br />

module (temperature range, standard; Ni 100)<br />

Temperature range<br />

standard<br />

Ni 100<br />

in C<br />

Decimal Hexadecimal Range<br />

> 295.0 32767 7FFFH Overflow<br />

295.0<br />

:<br />

250.1<br />

250.0<br />

:<br />

-60.0<br />

-60.1<br />

:<br />

-105.0<br />

2950<br />

:<br />

2501<br />

2500<br />

:<br />

-600<br />

-601<br />

:<br />

-1050<br />

SIMATIC S7 Ex Analog Modules<br />

686H<br />

:<br />

9C5H<br />

9C4H<br />

:<br />

FDA8H<br />

FDA7H<br />

:<br />

FF97H<br />

Overrange 1)<br />

Rated range<br />

Underrange 1)<br />

< - 105.0 -32768 8000H Underflow<br />

1) The characteristic of the Ni 100 sensor is not defined in the overrange and<br />

underrange. The rise of the characteristic curve is retained on leaving the linearized<br />

rated range. It is not possible to specify the accuracy of these ranges.<br />