SIMATIC S7 Ex Analog Modules<br />

Parameters of<br />

analog input<br />

modules<br />

3-42<br />

Tables 3-21 and 3-22 provide an overview of the parameters for analog input<br />

modules and show what parameters<br />

are static or dynamic and<br />

can be set for the modules as a whole or for a channel group or a channel.<br />

Table 3-21 Parameters of analog input module SM 331; AI 8 x TC/4 x RTD<br />

Parameter Value range Default Type of<br />

Effective Effect ve<br />

Basic settings<br />

Enable<br />

parameters range<br />

Diagnostic interrupt yes/no no<br />

Hardware interrupt on<br />

exceeding limit<br />

yes/no no<br />

Dynamic Module<br />

Hardw. inter. at end of cycle yes/no no<br />

Limit<br />

Upper limit<br />

from 32511 to - 32512<br />

32767 Dynamic Channel<br />

Lower limit<br />

from - 32512 to 32511<br />

- 32768<br />

Diagnostics<br />

Enable<br />

yes/no<br />

no Static Channel<br />

Wire break monitoring yes/no<br />

no<br />

group<br />

Measurement<br />

Interference frequency 400 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz Dynamic Channel<br />

suppression<br />

group<br />

Measurement mode – Deactivated<br />

– Voltage<br />

– Resistance 4-wire configuration<br />

– Thermal resistance (RTD)<br />

with linearization 4-wire<br />

configuration<br />

– Thermocouple with linearization and<br />

compensation to 0oC – Thermocouple with linearization and<br />

compensation to 50oC – Thermocouple with linearization and<br />

internal compensation<br />

– Thermocouple with linearization and<br />

external compensation 1)<br />

Voltage Dynamic Channel<br />

group<br />

Ranges See Tables 3-32 to 3-34 1V Dynamic Channel gr.<br />

1) Following types of compensation are possible with this measurement method:<br />

– Use of a compensation box<br />

The compensation box must correspond to the connected type of thermocouple.<br />

All thermocouples must be of the same type.<br />

– Use of a thermal resistor for compensation (e.g. Pt 100)<br />

The absolute terminal temperature is determined for compensation with a Pt 100 resistor in the climatic range.<br />

In this case, the thermocouples to be compensated can be of different types.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04