SIMATIC S7 HART Analog Modules<br />

4.8.1 Parameter Data Records<br />

Structure of the<br />

parameter data<br />

records for the<br />

HART analog input<br />

modules<br />

4-26<br />

Figures 4-10 and 4-11 show data record 0 for the static parameters and data<br />

record 1 for the dynamic parameters for AI HART and AO HART. In the case<br />

of S5 and the norm master, all the parameters are transferred to data record 0.<br />

7 6 5 4 3 2 1 0<br />

Parameter data record 0<br />

Byte 0 0 0 0 0 0 0 Group diagnostics<br />

Byte 1 0 0 0 0 0 0 Wire break check<br />

Channel 0<br />

Channel 1<br />

Byte 0<br />

Byte 1<br />

Byte 2<br />

Byte 3<br />

Byte 4<br />

Byte 5<br />

Byte 6<br />

to 9<br />

Byte 10<br />

to 13<br />

7 6 5 4 3 2 1 0<br />

Parameter data record 1<br />

0 0 0 0 0<br />

Hardware interrupt at end of cycle<br />

Enable diagnostic interrupt<br />

Enable limit interrupt<br />

2#00 = 2.5 ms<br />

0 0 0 0<br />

Integration time<br />

2#01 = 16.7 ms<br />

2#10 = 20 ms<br />

Channel 1 Channel 0<br />

2#11 = 100 ms<br />

must be 0<br />

must be 0<br />

M. type, m. range, channel 1<br />

M. type, m. range, channel 0<br />

see<br />

following<br />

Table 4-11<br />

Upper limit value, channel 0<br />

Lower limit value, channel 0<br />

Upper limit value, channel 1<br />

Lower limit value, channel 1<br />

Fig. 4-10 Parameters of the HART analog input module<br />

First “High-<br />

Byte,” then<br />

“Low-Byte”<br />

Table 4-11 Codes for the measurement type and measuring range for HART analog<br />

input module<br />

Measurement type Code Measuring range Code<br />

Deactivated 2#0000 Deactivated 2#0000<br />

4-wire transducer 2#0010 0 to 20 mA<br />

4 to 20 mA<br />

2#0010<br />

2#0011<br />

2-wire-transducer 2#0011 4 to 20 mA 2#0011<br />

HART (2-wire or<br />

4-wire transducer<br />

can be connected.)<br />

2#0111<br />

4 to 20 mA HART<br />

All commands permitted,<br />

and monodrop operation.<br />

2#1100<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04