SIMATIC S7 HART Analog Modules<br />

4.3.1 Setting Up the HART Analog Module and Field Devices<br />

Configuring and<br />

assigning<br />

parameters<br />

4-8<br />

The HART analog modules are configured and assigned parameters with<br />

STEP 7 and the connected smart field devices using the parameter<br />

assignment tool SIMATIC PDM:<br />

Steps<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

Plug the HART analog module into the<br />

ET200M distributed I/O system. Configure and<br />

assign parameters to the station in the<br />

SIMATIC Manager using STEP 7:<br />

Start by double-clicking the “Hardware” icon.<br />

Select the ET 200M distributed I/O system with<br />

an IM153-2 from the PROFIBUS catalog and<br />

attach this to the PROFIBUS (note the slave<br />

address).<br />

Insert the HART analog input module “AI HART”<br />

or “AO HART” into the desired slot and assign<br />

parameters to it (Parameters, see Section 4.4):<br />

Start by double-clicking the HART analog<br />

module in the selected slot.<br />

Download the configuration for the station which<br />

also contains the parameters for the HART<br />

analog input module to the programmable logic<br />

controller.<br />

To assign field device parameters with SIMATIC<br />

PDM, select the channel to which the field<br />

device is connected:<br />

Begin by double-clicking channel 0 (line 2) or<br />

channel 1 (line 3) of the HART analog module.<br />

Now you can use the SIMATIC PDM parameter<br />

assignment tool to assign parameters to the field<br />

devices: SIMATIC PDM provides you with a<br />

device- specific parameter assignment interface<br />

- depending on the type of field device<br />

connected. Field devices must first be made<br />

known via the supplied. GSE file.<br />

Fig. 4-5 Configuring and assigning parameters<br />

STEP7<br />

SIMATIC<br />

PDM<br />

I/O Modules with Intrinsically-Safe Signals<br />