3.6.4 Diagnostics of Analog Modules<br />

Introduction<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

A comparison of the analog modules with regard to their diagnostic messages<br />

is described in this section.<br />

What is diagnostics With the aid of the diagnostics function, you can determine whether analog<br />

processing is faulty or free of faults and what faults have occurred. On<br />

detecting a fault, the analog modules output the signal value ”7FFFH”<br />

irrespective of the parameterization.<br />

Parameterizing<br />

diagnostics<br />

Diagnostics is parameterized with STEP 7.<br />

SIMATIC S7 Ex Analog Modules<br />

Diagnostic evaluation A differentiation is made with regard to diagnostic evaluation between<br />

configurable and non-configurable diagnostic messages. In the case of the<br />

configurable diagnostic messages, evaluation only takes place when<br />

diagnostics has been enabled by means of parameterization (”diagnostic<br />

enable” parameter). The non-paramaterizable diagnostic messages are always<br />

evaluated irrespective of the diagnostic enable.<br />

Diagnostic messages trigger following actions:<br />

SF LED on analog module lights,<br />

if applicable channel fault LED,<br />

transfer of diagnostic message to CPU,<br />

diagnostic interrupt triggered (only if diagnostic interrupt has been<br />

enabled in the parameterization).<br />