Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The discussion of safety-relevant aspects is limited to the direct comparison<br />

of the data for inductance and capacity (Tables 1-5 and 1-6).<br />

Table 1-5 Comparison of data for inductance and capacity<br />

Ex module Comparison Lightning<br />

arrester 1<br />

Cable Lightning<br />

arrester 2<br />

Sensor/<br />

actuator<br />

La LBD1 +LLtg +LBD2 +Li<br />

Ca x CBD1 +CLtg +CBD2 +Ci<br />

Table 1-6 Example of the comparison of data for inductance and capacity<br />

Ex module Comparison Lightning<br />

arrester 1<br />

Cable Lightning<br />

arrester 2<br />

Sensor/<br />

actuator<br />

La = 4 mH 0.5 H 50 H 0.5 mH 0.6 mH<br />

Ca = 270 nF 1 nF 10 nF 6 nF 6 nF<br />

The overvoltage protection elements described in this section are only<br />

effective if used together with external lightning protection. External<br />

lightning protection measures reduce the effects of a lightning strike.<br />

You will find suitable lightning protection elements for Ex modules in the<br />

manuals specified in the foreword.<br />