SIMATIC S7 Ex Analog Modules<br />

Temperature range<br />

type B<br />

3-20<br />

Table 3-19 shows the representation of the digitized measured value for the<br />

temperature range, sensor type B.<br />

Table 3-19 Representation of the digitized measured value of an analog input<br />

module (temperature range, type B)<br />

Temperature<br />

range in C<br />

type B<br />

Decimal Hexadecimal Range<br />

> 2070.0 32767 7FFFH Overflow<br />

2070.0<br />

:<br />

1820.1<br />

1820.0<br />

:<br />

:<br />

200.0 1)<br />

:<br />

0.0<br />

-0.1<br />

:<br />

-150.0<br />

20700<br />

:<br />

18201<br />

18200<br />

:<br />

:<br />

2000<br />

:<br />

0<br />

-1<br />

:<br />

-1500<br />

50DCH<br />

:<br />

4719H<br />

4718H<br />

:<br />

:<br />

7D0H<br />

:<br />

0H<br />

FFFFH<br />

:<br />

FF24H<br />

Overrange 2)<br />

Rated range<br />

Underrange 2)<br />

< -150.0 -32768 8000H Underflow<br />

In the case of incorrect wiring (e.g. polarity reversal, open inputs) or a sensor fault in<br />

the negative range (e.g. incorrect type of thermocouple), on dropping below FA24H<br />

the analog input module signals underflow and outputs 8000H.<br />

1) The module linearizes the range from +1820 to -200C for type B. Below -200C,<br />

the rise of the characteristic curve decreases to such an extent that, from this point,<br />

precision evaluation is no longer possible. The rise in the characteristic curve at this<br />

point is retained until underrange is reached.<br />

The characteristic curve of the thermocouple does not feature monotone<br />

characteristics in the temperature range between 0 and 40 C. Measured values<br />

from this range are not distinctly allocated to a specific temperature.<br />

2) The characteristic of the thermocouple is not defined in the overrange and<br />

underrange. The rise of the characteristic curve is retained on leaving the linearized<br />

range. It is not possible to specify the accuracy of these ranges.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04