SIMATIC S7 Ex Digital Modules<br />

Diagnostics of the<br />

digital input<br />

module<br />

Reading out<br />

diagnostic<br />

messages<br />

2-10<br />

Table 2-5 provides an overview of the diagnostic messages of the SM 321;<br />

DI 4 x NAMUR. You enable diagnostics in STEP 7 (see Table 2-3).<br />

The diagnostics information refers to either the channel groups or the entire<br />

module.<br />

Table 2-5 Diagnostic messages of SM 321; DI 4 x NAMUR<br />

Wire break<br />

Short to M<br />

Diagnostic message Effective range of<br />

diagnostics<br />

Incorrect parameters in module<br />

Module not parameterized<br />

No external auxiliary supply<br />

No internal auxiliary supply<br />

Fuse blown<br />

Watchdog triggered<br />

EPROM error<br />

RAM error<br />

CPU error<br />

Hardware interrupt lost<br />

configurable<br />

Channel group yes<br />

Module no<br />

You can read out system diagnostics with STEP 7. You can read detailed<br />

diagnostic messages from the module in the user program with SFC 59 (refer<br />

to /235/).<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04