SIMATIC S7 HART Analog Modules<br />

4.2.2 How to Use HART<br />

System<br />

environment<br />

Field device with HART functionality<br />

4-6<br />

HART hand-held device<br />

To use a smart field device with HART functionality, you require the<br />

following system environment (see Figure 4-3):<br />

Current loop 4 - 20 mA<br />

HART parameter assignment tool:<br />

You can set the HART parameters either with an external hand-held<br />

controller (HART hand-held device) or by using a HART parameter<br />

assignment tool. The parameter assignment tool accesses the HART<br />

analog module directly, whereas the HART hand-held device is connected<br />

parallel to the field device. The PDM (Process Device Manager) can be<br />

obtained as an autonomous tool (stand alone) or it can be embedded in<br />

STEP7 HW Config. For the latter, an optional package is required.<br />

How HART is linked to the system:<br />

The HART analog module assumes the function of a “master,” in that it<br />

receives the commands from the HART parameter assignment tool,<br />

forwards them to the field device, and then sends back the responses. The<br />

interface of the HART analog module comprises data records which are<br />

transmitted via the I/O bus. The data records must be created and<br />

interpreted by the HART parameter assignment tool.<br />

Interface connection for HART parameter assignment tool:<br />

DP Connection which is capable of master class 1 as well as master<br />

class 2 functionality.<br />

4...20 mA<br />

Fig. 4-3 System environment required for HART<br />

Error handling<br />

HART resistance<br />

Modem<br />

L+: 24V<br />

Analog to digital conversion<br />

ADC<br />

of the cyclic measured<br />

value<br />

G : Ground<br />

HART analog module<br />

Filtering out of<br />

HART signal<br />

Interface<br />

connection to<br />

PROFIBUS<br />

SIMATIC<br />

PDM<br />

HART parameter assignment tool<br />

The two HART status bytes transmitted with each response of the field<br />

device contain error information relating to HART communication, HART<br />

commands and device status, (see HART communication data records,<br />

Section 4.8.3).<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04