4.5 Diagnostics and Interrupts of HART Analog Modules<br />

4.5.1 Diagnostic Functions of HART Analog Modules<br />

Overview of<br />

diagnostic<br />

functions<br />

Diagnostic<br />

messages<br />

Causes of errors<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

If errors occur during configuration and parameter assignment or during the<br />

operating phase, you can use diagnostics to determine the cause of the error.<br />

The general diagnostic behavior of the HART analog module corresponds to<br />

that of the other SIMATIC S7-Ex analog modules, see Section 3.6.4.<br />

The diagnostic messages for the analog input modules are shown in<br />

Table 3-24 of Section 3.6.4; the diagnostic messages for the analog output<br />

modules are shown in Table 3.6.4. The additional diagnostic messages are<br />

listed in the following table:<br />

Table 4-6 Additional diagnostic messages for the analog input module<br />

SM 331; AI 2 x 0/4...20mA HART and the analog output module<br />

SM 332; AO 2 x 0/4...20mA HART<br />

Diagnostic message Effective range of<br />

diagnostics<br />

Modification of HART parameters<br />

reported by the connected field<br />

device<br />

channel<br />

Configurable with<br />

group diagnostics<br />

HART group error yes<br />

The following table provides a list of possible causes and corresponding<br />

corrective measures for the individual diagnostic messages.<br />

Table 4-7 Additional diagnostic messages, possible causes of the errors, and corrective measures<br />

Diagnostic message Possible cause of error / diagnostics Corrective measures<br />

Modification of HART<br />

parameters reported by the<br />

connected field device<br />

The identifier for the modification of<br />

parameters to the HART field device was<br />

set in the HART device status.<br />

HART group error Communication and command error<br />

during HART operation affecting the<br />

connected HART field devices.<br />

SIMATIC S7 HART Analog Modules<br />

yes<br />

If you do not want diagnostic interrupts<br />

to be triggered when parameters are<br />

modified, you should disable the<br />

diagnostic interrupt.<br />

For detailed information, evaluate the<br />

response data record of the relevant client<br />

(see 4.8.3) or the additional diagnostic<br />

data record (see 4.8.4)<br />

4-13