Safety data (refer to Certificate of Conformity in<br />

Appendix A)<br />

Maximum values of output<br />

circuits (per channel)<br />

U0 (no-load output<br />

voltage)<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

max. 15.75 V<br />

I0 (short-circuit current) max. 85 mA<br />

P0 (load power) max. 335 mW<br />

L0 (permissible external<br />

inductance)<br />

max. 5 m<br />

C0 (permissible external<br />

capacitance)<br />

max. 500 nF<br />

Um (error voltage) max. 60 V DC<br />

30 V AC<br />

Ta (permissible ambient<br />

temperature)<br />

max. 60C<br />

Data for actuator selection<br />

Outputs<br />

No-load voltage UA0<br />

Internal resistance RI<br />

Curve vertices E<br />

Voltage UE<br />

Current IE<br />

Parallel connection<br />

of 2 outputs<br />

15 V DC 5%<br />

200 5%<br />

10 V DC 10%<br />

20.5 mA 10%<br />

For redundant activation of<br />

a load<br />

Not possible<br />

For increasing power Possible, see Manual<br />

“S7-300, M7-300, ET<br />

200M Automation<br />

Systems Principles of<br />

Intrinsically-Safe<br />

Design” Section<br />

”Intrinsically-Safe<br />

Circuit with Two or<br />

More Items of<br />

Associated Electrical<br />

Apparatus<br />

(Requirements for<br />

Installation in Zones 0<br />

and 1)”<br />

Switching frequency<br />

At resistive load 100 Hz<br />

At inductive load (L