22.07.2013 Views

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3.1.3 Analog Value Representation for the Output Ranges of Analog<br />

Outputs<br />

Current output<br />

ranges<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 3-20 shows the representation of the current output ranges 0 to 20 mA<br />

and 4 to 20 mA.<br />

Table 3-20 Representation of analog output range of analog output modules (current output ranges)<br />

Output<br />

range<br />

0 to 20 mA<br />

Output<br />

Units Range<br />

range<br />

4 to 20 mA Decimal Hexadecimal<br />

0.0 0.0 32512 7F00H Overflow<br />

23.515 22.81 32511 7EFFH<br />

: : : : Overrange<br />

20.0007 20.005 27649 6C01H<br />

20.000 20.000 27648 6C00H<br />

: : : : Rated range<br />

0.0 4.000 0 0H<br />

0.0 3.9995 -1 FFFFH<br />

: : : Underrange<br />

0.0 - 6912 E500H<br />

0.0 - 6913 E4FFH<br />

: : Underflow<br />

- 32768 8000H<br />

SIMATIC S7 Ex Analog Modules<br />

Note<br />

In the analog output SM 332; AO 4 x 0/4...20 mA, the linearity can decrease<br />

in the overrange at load resistances 425 .<br />

3-21