4.4 Parameters of HART Analog Modules<br />

Overview of the<br />

parameters<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 4-4 lists the parameters for the HART analog input module, Table 4-5<br />

lists the parameters for the HART analog output module. The tables show<br />

which parameters can be set for the module as a whole and which parameters<br />

can be set separately for each channel. General information on assigning<br />

parameters can be found in the description of the SIMATIC-Ex analog<br />

modules in Chapter 3.6.3.<br />

Table 4-4 Parameters for the analog input module SM 331; AI 2 x 0/4...20mA HART<br />

Parameter Range of values Default Type of<br />

Effective Effect ve<br />

Basic settings<br />

Enable<br />

setting parameter range<br />

Diagnostic interrupt yes/no no<br />

Hardware interrupt on yes/no no<br />

exceeding limit<br />

dynamic y module<br />

Hardware interrupt at end of<br />

cycle<br />

yes/no no<br />

Trigger for hardware interrupt<br />

Upper limit<br />

20 ...0/4 mA (from 32511 to -32512) – ( 32767)* dynamic channel<br />

Lower limit<br />

0/4 ...20 mA (from -32512 to 32511) – (-32768)*<br />

Diagnostics<br />

<br />

<br />

Group diagnostics<br />

Wire break monitoring<br />

yes/no<br />

yes/no<br />

no<br />

no<br />

static channel<br />

Measurement<br />

Measurement mode deactivated<br />

4DMU current (4-wire transducer)<br />

2DMU current (2-wire transducer)<br />

HART (connected to 2DMU or<br />

4DMU)<br />

HART dynamic channel<br />

Range of measurement 0...20mA (can only be set at 4DMU),<br />

4...20mA<br />

4...20mA dynamic channel<br />

Integration time 2.5ms; 16.6ms; 20ms; 100ms<br />

corresponds to interference<br />

frequency suppression of 400Hz;<br />

60Hz; 50Hz; 10Hz<br />

20ms dynamic channel<br />

*) Values in parenthesis can be set with SFC dynamic parameterization.<br />

SIMATIC S7 HART Analog Modules<br />