SIMATIC S7 Ex Digital Modules<br />

Reading out<br />

diagnostic<br />

messages<br />

Faults and<br />

corrective<br />

measures<br />

2-22<br />

You can read out system diagnostics with STEP 7. You can read detailed<br />

diagnostic messages from the module in the user program with SFC 59 (refer<br />

to /235/).<br />

Table 2-12 provides a list of possible causes, marginal conditions for fault<br />

recognition and corresponding corrective measures for individual diagnostic<br />

messages.<br />

Bear in mind that, in order to detect faults which are indicated by means of<br />

configurable diagnostic messages, must also be parameterized accordingly.<br />

Table 2-12 Diagnostic messages as well as fault causes and corrective measures for<br />

SM 322; DO 4 x 24V/10mA and SM 322; DO 4 x 15V/20mA<br />

Diagnostic message Fault<br />

recognition<br />

at<br />

Possible fault cause Corrective measures<br />

Chassis ground Only when Output overload Eliminate overload<br />

short-circuit h t i it<br />

output t t at t ”1”<br />

Short-circuit between the<br />

two output lines<br />

Eliminate short-circuit<br />

Wire break Only when<br />

output at ”1”<br />

No-load voltage Only when<br />

output at ”1”<br />

Incorrect parameters<br />

in module<br />

Module not<br />

parameterized<br />

No external auxiliary<br />

supply<br />

No internal auxiliary<br />

supply<br />

Conductor break between<br />

module and actuator<br />

Make conductor connection<br />

Channel not used (open) Disable channel by<br />

parameterization<br />

”diagnostics wire break”<br />

Failure of internal channel<br />

supply voltage<br />

General Invalid parameters loaded in<br />

module by means of SFC<br />

General Invalid parameters loaded in<br />

module by means of SFC<br />

General No L+ supply voltage of<br />

module<br />

General No L+ supply voltage of<br />

module<br />

Module-internal fuse<br />

defective<br />

Fuse blown General Module-internal fuse<br />

defective<br />

Time watchdog<br />

tripped<br />

EPROM error<br />

RAM error<br />

General High electromagnetic<br />

interference at times<br />

Replace module<br />

Check parameterization of<br />

module and re-load valid<br />

parameters<br />

Check parameterization of<br />

module and re-load valid<br />

parameters<br />

Supply L+<br />

Supply L+<br />

Replace module<br />

Replace module<br />

Eliminate interference<br />

sources and switch CPU<br />

supply voltage OFF/ON<br />

CPU error Module defective Replace module<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04