SIMATIC S7 Ex Digital Modules<br />

Safety data (refer to Certificate of Conformity in<br />

Appendix A)<br />

Maximum values of input<br />

circuits (per channel)<br />

U0 (no-load output<br />

voltage)<br />

max. 10 V<br />

I0 (short-circuit<br />

current)<br />

max. 14.1 mA<br />

P0 (load power) max. 33.7 mW<br />

L0 (permissible<br />

external<br />

inductance)<br />

max. 100 m<br />

C0 (permissible<br />

external<br />

capacitance)<br />

max. 3 F<br />

Um (error voltage) max. 60 V DC<br />

30 V AC<br />

Ta (permissible<br />

ambient<br />

temperature)<br />

max. 60C<br />

2-6<br />

Data for sensor selection<br />

In accordance with DIN 19234 or NAMUR<br />

Input current<br />

at signal ”1” 2.1 to 7 mA<br />

at signal ”0” 0.35 to 1.2 mA<br />

Time/frequency<br />

Interrupt conditioning time<br />

for<br />

Interrupt conditioning<br />

only<br />

Interrupt and<br />

diagnostic<br />

conditioning<br />

Input delay (EV)<br />

configurable yes<br />

max. 250 s<br />

max. 250 s<br />

Nominal value typical 0.1/0.5/3/15/20ms<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04