Error limits of analog inputs for thermocouples<br />

(at 25oC ambient temperature and<br />

100 ms integration time)<br />

Type Temperature range Basic<br />

error 1)<br />

T -150 o C .... +400 o C<br />

-230 o C .... -150 o C<br />

U -50 o C .... +400 o C<br />

-200 o C .... -50 o C<br />

E -100 o C .... +1000 o C<br />

-200 o C .... -100 o C<br />

J -150 o C .... +1200 o C<br />

-210 o C .... -150 o C<br />

L -50 o C .... +1200 o C<br />

-200 o C .... -50 o C<br />

K -100 o C .... +1372 o C<br />

-220 o C .... -100 o C<br />

N -50 o C .... +1300 o C<br />

-150 o C .... -50 o C<br />

R +200 o C .... +1769 o C<br />

-50 o C .... +200 o C<br />

S +100 o C .... +1769 o C<br />

-50 o C .... +100 o C<br />

B +700 o C .... +1820 o C<br />

+500 o C .... +700 o C<br />

+200 o C .... +500 o C<br />

0.2K<br />

1K<br />

0.2K<br />

1K<br />

0.2K<br />

1K<br />

0.2K<br />

0.5K<br />

0.2K<br />

1K<br />

0.2K<br />

1K<br />

0.2K<br />

1K<br />

0.3K<br />

1K<br />

0.3K<br />

1K<br />

0.3K<br />

0.5K<br />

3K<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Temperature<br />

error 2)<br />

[ o C/K]<br />

0.006<br />

0.006<br />

0.0075<br />

0.02<br />

0.02<br />

0.018<br />

0.025<br />

0.025<br />

0.025<br />

0.04<br />

Error limits of analog inputs for thermal resistors<br />

(at 25oC ambient temperature and<br />

100 ms integration time)<br />

Type Temperature range Basic<br />

error 1)<br />

Pt 100 -200 o C ....+325 o C<br />

Climatic<br />

Pt 200 -200 o C ....+325 o C<br />

Climatic<br />

Ni 100 -60 o C ....+250 o C<br />

Climatic<br />

Pt 100 -200 o C ....+850 o C<br />

Standard<br />

Pt 200 -200 o C ....+850 o C<br />

Standard<br />

Ni 100 -60 o C ....+250 o C<br />

Standard<br />

SIMATIC S7 Ex Analog Modules<br />

Temperature<br />

error 2)<br />

[ o C/K]<br />

0.05K 0.006<br />

0.05K 0.006<br />

0.05K 0.003<br />

0.2K 0.01<br />

0.2K 0.01<br />

0.1K 0.003<br />

Error limits of analog inputs for resistance sensors<br />

(at 25oC ambient temperature and<br />

100 ms integration time)<br />

Type Resistant sensor Basic<br />

error 3)<br />

Temperature<br />

error 2)<br />

[%/K]<br />

150 0.000 ...176.383 0.006% 0.001<br />

300 0.000 ...352.767 0.006% 0.001<br />

6000.000 ...705.534 0.006% 0.001<br />

1) The basic error includes the linearization error of the voltage temperature conversion and the basic error of the<br />

analog/digital conversion at Tu = 25oC. 2) The total temperature error = temperature error x max. ambient temperature change Tu as temperature difference<br />

with respect to 25oC .<br />

3) The basic error includes the error in % of the measuring range of the analog/digital conversion at Tu = 25oC. The operating error for the use of thermocouples/thermal resistors consists of:<br />

– Basic error of analog input at Tu = 25oC – Total temperature error<br />

– Errors which occur due to compensation of the reference junction temperature<br />

– Error of the thermocouple/thermal resistor used<br />

The operating error for use of resistant sensors consists of:<br />

– Basic error of analog input at Tu = 25oC – Total temperature error<br />

– Error of sensor used<br />

3-61