SIMATIC S7 Ex Analog Modules<br />

Diagnostics of<br />

analog input<br />

modules<br />

Faults and<br />

corrective<br />

measures<br />

3-46<br />

Table 3-24 provides an overview of the paramterizable diagnostic messages<br />

of the analog input modules. The enable is set in the “diagnostics” parameter<br />

block (see Section 3.6.3). Diagnostic information is assigned to the<br />

individual channels or the entire module.<br />

Table 3-24 Diagnostic messages of analog input modules SM 331;<br />

AI 8 x TC/4 x RTD, AI 4 x 0 / 4...20 mA and AI 2 x 0/4...20 mA HART<br />

Diagnostic message Effective range<br />

of diagnostics<br />

configurable<br />

Wire break 1) yes<br />

Underrange<br />

Overrange Channel<br />

Reference channel fault 2)<br />

yes,<br />

jointly j y<br />

for all 3 faults<br />

Incorrect parameters in module no<br />

Incorrect parameters in module<br />

Module not parameterized<br />

No external auxiliary voltage 3)<br />

No internal auxiliary voltage 3)<br />

Fuse blown 3)<br />

Watchdog triggered Module no<br />

EPROM error 4)<br />

RAM error 4)<br />

CPU error 4)<br />

ADU error 4)<br />

Hardware interrupt lost<br />

1) If wire break diagnostics is enabled, the modules AI 4 x 0 / 4...20 mA and<br />

AI 2 x 0/4...20 mA output the wire break message for the connected 2-wire transducer<br />

(4...20 mA) if the input current drops below a value of I3.6 mA (wire break limits<br />

in accordance with NAMUR). For the digital measured value, see Figure 3-4.<br />

In the case of the module AI 8 x TC/4 x RTD the line is checked by connecting a test<br />

current if wire break diagnostics is enabled. The wire break message is only<br />

deactivated (hysteresis), when the input current rises above 3.8 mA again.<br />

2) Only for thermocouples with external compensation and compensation fault.<br />

3) Only for AI 4 x 0 / 4...20 mA and AI 2 x 0/4...20 mA HART with 24 volt supply from<br />

L+.<br />

4) The tests are conducted during start-up and on-line.<br />

Table 3-25 provides a list of possible causes and corresponding corrective<br />

measures for individual diagnostic messages.<br />

Bear in mind that, in order to detect faults which are indicated by means of<br />

configurable diagnostic messages, the module must also be parameterized<br />

accordingly.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04