Table 3-25 Diagnostic messages of analog input modules SM 331; AI 8 x TC/4 x RTD, AI 4 x 0 / 4...20 mA and<br />
AI 2 x 0/4...20 mA HART their possible causes and corrective measures<br />
Diagnostic message Possible fault cause Corrective measures<br />
Wire break Break in line between module and sensor Connect line<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04<br />
Channel not connected (open) Deactivate channel group (”Measurement<br />
mode parameter)<br />
Measuring range underflow Input value below underflow range, fault<br />
possibly caused by:<br />
on AI 8 x TC/4 x RTD – Incorrect type of thermocouple<br />
– Sensor connected with reversed<br />
polarity<br />
– incorrect measuring range selected<br />
on AI 4 x 0 / 4...20 mA – Module does not signal<br />
measuring range underflow<br />
– Sensor connected with reversed<br />
polarity;<br />
(a digitized value is output for<br />
0 mA)<br />
– Check type of thermocouple<br />
– Check connection terminals<br />
– Parameterize different measuring range<br />
Measuring range overflow Input value exceeds overflow range Parameterize different measuring range<br />
Reference channel fault Measuring channel has different type of<br />
sensor parameterized as reference<br />
channel<br />
Incorrect parameters in<br />
module<br />
Parameterize different type of sensor<br />
Fault in reference channel (e.g. wire Eliminate fault in reference channel<br />
break) values of all measuring channels<br />
set to 7FFFH<br />
Module supplied with invalid parameters Check parameterization of module and<br />
re-load valid parameters<br />
Module not parameterized Module not supplied with parameters Include module in parameterization<br />
No external auxiliary voltage No module supply voltage L+ Provide L+ supply<br />
No internal auxiliar y voltage No module supply voltage L+ Provide L+ supply<br />
Module-internal fuse defective Replace module<br />
Fuse blown Module-internal fuse defective Replace module<br />
Time watchdog tripped In part, high electromagnetic interference Eliminate interference sources<br />
Module defective Replace module<br />
EPROM error<br />
In part, high electromagnetic interference Eliminate interference sources and switch<br />
RAM error<br />
CPU supply voltage OFF/ON<br />
CPU error<br />
ADU error Module defective Replace module<br />
Hardware interrupt lost Successive hardware interrupts (limits<br />
exceeded, end of cycle interrupt) occur<br />
faster than the CPU can process them<br />
SIMATIC S7 Ex Analog Modules<br />
Change interrupt processing in CPU and<br />
reparameterize module if necessary<br />
3-47