SIMATIC S7 HART Analog Modules<br />
SM 331;AI 2 x 0/4...20 mA HART<br />
Dimensions and weight<br />
Dimensions W x H x D (mm) 40 x 125 x 120<br />
Weight approx. 260 g<br />
Module-specific data<br />
Number of inputs<br />
2<br />
Number of power outputs 2<br />
Line length, shielded max. 400 m<br />
Type of protection KEMA<br />
(see Appendix A)<br />
4-18<br />
[EEx ib] <strong>II</strong>C to<br />
EN 50020<br />
KEMA test number 97ATEX3039 X<br />
Voltages, currents, potentials<br />
Bus power supply<br />
Rated load voltage L +<br />
Reverse voltage protection<br />
5 V DC<br />
24 V DC<br />
yes<br />
Power supply for 2-wire<br />
transducer<br />
Short-circuit proof yes (approx. 30 mA)<br />
Galvanic isolation<br />
Between channels and<br />
backplane bus<br />
yes<br />
Between the channels yes<br />
Between channels and load<br />
voltage L+<br />
yes<br />
Between backplane bus<br />
and load voltage L+<br />
yes<br />
Permissible difference in potential (UISO) for signals<br />
from a hazardous area<br />
Between channels and<br />
backplane bus<br />
Between channels and load<br />
voltage L+<br />
60 V DC<br />
30 V AC<br />
60 V DC<br />
30 V AC<br />
Between channels 60 V DC<br />
30 V AC<br />
Between backplane bus<br />
and load voltage L+<br />
60 V DC<br />
30 V AC<br />
Voltages, currents, potentials continued<br />
Permissible difference in potential (UISO) for signals<br />
from non-hazardous area<br />
Between channels and<br />
backplane bus<br />
Between channels and load<br />
voltage L+<br />
400 V DC<br />
250 V AC<br />
400 V DC<br />
250 V AC<br />
Between channels 400 V DC<br />
250 V AC<br />
Between backplane bus<br />
and load voltage L+<br />
75 V DC<br />
60 V AC<br />
Insulation tested<br />
Channels to backplane bus<br />
and load voltage L+<br />
with 1500 V AC<br />
Channels to each other with 1500 V AC<br />
Between load voltage L+<br />
and backplane bus<br />
with 500 V DC<br />
Current input<br />
From backplane bus<br />
From load voltage L +<br />
max. 100 mA<br />
max. 180 mA<br />
Module power loss typically 4.5 W<br />
Safety data (see Certificate of Conformity in<br />
Appendix A)<br />
Type of protection to<br />
EN 50020<br />
Maximum values per channel<br />
U0 (no-load output<br />
voltage)<br />
[EEx ib] <strong>II</strong>C<br />
max. 29.6 V<br />
I0 (short-circuit current) max. 99 mA<br />
P0 (load power) max. 553 mW<br />
L0 (permissible external<br />
inductance)<br />
max. 3 m<br />
C0 (permissible external<br />
capacitance)<br />
max. 62 nF<br />
Um (error voltage) max. 250 V DC<br />
Ta (permissible ambient<br />
temperature)<br />
0 to 60C<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04