SIMATIC S7 HART Analog Modules<br />

SM 331;AI 2 x 0/4...20 mA HART<br />

Dimensions and weight<br />

Dimensions W x H x D (mm) 40 x 125 x 120<br />

Weight approx. 260 g<br />

Module-specific data<br />

Number of inputs<br />

2<br />

Number of power outputs 2<br />

Line length, shielded max. 400 m<br />

Type of protection KEMA<br />

(see Appendix A)<br />

4-18<br />

[EEx ib] <strong>II</strong>C to<br />

EN 50020<br />

KEMA test number 97ATEX3039 X<br />

Voltages, currents, potentials<br />

Bus power supply<br />

Rated load voltage L +<br />

Reverse voltage protection<br />

5 V DC<br />

24 V DC<br />

yes<br />

Power supply for 2-wire<br />

transducer<br />

Short-circuit proof yes (approx. 30 mA)<br />

Galvanic isolation<br />

Between channels and<br />

backplane bus<br />

yes<br />

Between the channels yes<br />

Between channels and load<br />

voltage L+<br />

yes<br />

Between backplane bus<br />

and load voltage L+<br />

yes<br />

Permissible difference in potential (UISO) for signals<br />

from a hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and load<br />

voltage L+<br />

60 V DC<br />

30 V AC<br />

60 V DC<br />

30 V AC<br />

Between channels 60 V DC<br />

30 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

60 V DC<br />

30 V AC<br />

Voltages, currents, potentials continued<br />

Permissible difference in potential (UISO) for signals<br />

from non-hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and load<br />

voltage L+<br />

400 V DC<br />

250 V AC<br />

400 V DC<br />

250 V AC<br />

Between channels 400 V DC<br />

250 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

75 V DC<br />

60 V AC<br />

Insulation tested<br />

Channels to backplane bus<br />

and load voltage L+<br />

with 1500 V AC<br />

Channels to each other with 1500 V AC<br />

Between load voltage L+<br />

and backplane bus<br />

with 500 V DC<br />

Current input<br />

From backplane bus<br />

From load voltage L +<br />

max. 100 mA<br />

max. 180 mA<br />

Module power loss typically 4.5 W<br />

Safety data (see Certificate of Conformity in<br />

Appendix A)<br />

Type of protection to<br />

EN 50020<br />

Maximum values per channel<br />

U0 (no-load output<br />

voltage)<br />

[EEx ib] <strong>II</strong>C<br />

max. 29.6 V<br />

I0 (short-circuit current) max. 99 mA<br />

P0 (load power) max. 553 mW<br />

L0 (permissible external<br />

inductance)<br />

max. 3 m<br />

C0 (permissible external<br />

capacitance)<br />

max. 62 nF<br />

Um (error voltage) max. 250 V DC<br />

Ta (permissible ambient<br />

temperature)<br />

0 to 60C<br />

I/O Modules with Intrinsically-Safe Signals<br />