SIMATIC S7 Ex Analog Modules<br />

Non-insulated<br />

transducers<br />

3-24<br />

Non-insulated transducers are connected to the ground potential on site. Due<br />

to local conditions or interference, differences in potential (static or dynamic)<br />

can occur between the locally distributed test points. Equipotential bonding<br />

conductors should be provided between the test points in order to avoid these<br />

differences in potential.<br />

Fig. 3-2 shows the connection principle of non-insulated transducers to an<br />

isolated analog input module.<br />

Non-insulated<br />

transducers<br />

U CM<br />

U UCM max.<br />

U ISO<br />

Equipotential bonding<br />

conductor<br />

M+<br />

M-<br />

M+<br />

M-<br />

U ISO<br />

ADU<br />

Logic<br />

Ground bus<br />

P5V<br />

M internal<br />

CPU<br />

Backplane<br />

bus<br />

Fig. 3-2 Connection of non-insulated transducers to an isolated analog input module<br />

M<br />

L+<br />

M<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04