Analog output<br />

Output ranges<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

You can connect the outputs as:<br />

Current outputs<br />

The outputs can be set channel by channel. Output mode is parameterized<br />

with STEP 7.<br />

You can set the various output ranges for current outputs with STEP7.<br />

Table 3-38 shows the possible output ranges of the analog output module<br />

SM 332; AO 4 x 0/4...20 mA.<br />

Table 3-38 Output ranges of analog output module SM 332; AO 4 x 0/4...20 mA<br />

Selected output mode Explanation Output range<br />

Current The digitized analog values are specified in Section 3.1.3, Table 3-20<br />

Current measuring range.<br />

Wire break check<br />

Influence of load<br />

voltage drop on<br />

diagnostic<br />

message<br />

SIMATIC S7 Ex Analog Modules<br />

from 0 to 20 mA<br />

from 4 to 20 mA<br />

The analog output module SM 332; AO 4 x 0/4...20 mA carries out an wire<br />

break check.<br />

Conditions: A minimum output current of 100 A must flow and the<br />

voltage set at the load must be > 12 V in order to signal<br />

wire break.<br />

If the 24 V load voltage drops below the permissible rated range (< 20.4 V)<br />

the output current can be reduced before a diagnostic message is output if a<br />

load of 400 is connected and the output currents are 18 mA.<br />

3-71