Parameterization<br />

Default<br />

settings<br />

Configurable<br />

characteristics<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The parameters for the SM 322; DO 4 x 24V/10mA are set with STEP 7 .<br />

You must implement the settings in CPU STOP mode. During transfer from<br />

the PG to the S7-300, the parameters set in this way are stored in the CPU<br />

and then transferred by the CPU to the digital module.<br />

Alternatively, you can also change several parameters in the user program<br />

with SFCs 55 to 57 (see /235/).<br />

The parameters for the 2 parameterization alternatives are subdivided into:<br />

Static parameters<br />

Dynamic parameters<br />

Table 2-8 shows the characteristics of static and dynamic parameters.<br />

Table 2-8 Static and dynamic parameters<br />

SIMATIC S7 Ex Digital Modules<br />

Parameter Set with CPU status<br />

Static PG STOP<br />

dynamic PG STOP<br />

SFCs 55 to 57 in user<br />

program<br />

RUN<br />

The digital output features default settings for diagnostics, substitute values,<br />

etc. (see Table 2-10).<br />

These default settings are applicable when the digital module has not been<br />

parameterized with STEP 7 .<br />

The characteristics of the SM 322; DO 4 x 24V/10mA can be parameterized<br />

with the following parameter blocks:<br />

Basic settings<br />

Diagnostics<br />

2-19