3.6.6 Characteristics of Analog Modules<br />

Introduction<br />

Influence of<br />

supply voltage and<br />

operating status<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Described in this section:<br />

Dependency of the analog input and output values on the supply voltage<br />

of the analog module and the operating status of the CPU.<br />

Characteristics of the analog modules depending on the position of the<br />

analog values in the relevant value range.<br />

Influence of faults on the analog modules.<br />

The input and output values of the analog modules are dependent on the<br />

supply voltage of the analog module and on the operating status of the CPU.<br />

Table 3-28 provides an overview of these dependencies.<br />

Table 3-28 Dependencies of analog input/output values on the CPU operating status and the supply voltage L +<br />

CPU operating<br />

status<br />

POWER<br />

ON<br />

POWER<br />

ON<br />

POWER<br />

OFF<br />

Supply voltage<br />

L+ at analog<br />

module<br />

Input value of<br />

analog input modules<br />

RUN L + applied Process value CPU value<br />

7FFFH up to first conversion after<br />

switching on or after module<br />

parameterization has been<br />

completed<br />

No L + Overflow value 1) 0 mA<br />

STOP L + applied Process value Default/last value<br />

7FFFH up to first conversion after<br />

switching on or after module<br />

parameterization has been<br />

completed<br />

No L + Overflow value 1) 0 mA<br />

– L + applied – 0 mA<br />

No L + – 0 mA<br />

1) only applies to SM 331; AI 8xTC/4xRTD as no L+ supply voltage is required.<br />

SIMATIC S7 Ex Analog Modules<br />

Output value of<br />

analog output module<br />

Up to first conversion ...<br />

after switch-on has been<br />

completed if signal of 0 mA is<br />

output.<br />

after parameterization has<br />

been completed, previous value<br />

is output.<br />

at 0...20 mA: 0 mA default<br />

at 4...20 mA: 4 mA default<br />

Failure of the L+ supply voltage for the analog modules is always indicated<br />

by the group fault LED on the module and additionally entered in diagnostics.<br />