SIMATIC S7 Ex Digital Modules<br />
Digital output SM 322; DO 4 x 15V/20mA<br />
Dimensions and Weight<br />
Dimensions W x H x D (mm) 40 x 125 x 120<br />
Weight approx. 230 g<br />
Module-specific data<br />
Number of outputs 4<br />
Line length, shielded max. 200 m<br />
Type of protection PTB<br />
(see Appendix A)<br />
2-26<br />
[EEx ib] <strong>II</strong>C<br />
to EN 50020<br />
Test number Ex-96.D.2102 X<br />
Type of protection FM<br />
(see Appendix B)<br />
Voltages, currents, potentials<br />
Bus power supply<br />
Rated load voltage L+<br />
Reverse voltage protection<br />
Total current of outputs<br />
Horizontal arrangement up<br />
to 60 C<br />
Vertical arrangement up to<br />
40 C<br />
CL I, DIV 2,<br />
GP A, B, C, D T4<br />
5 V DC<br />
24 V DC<br />
yes<br />
No restrictions<br />
No restrictions<br />
Galvanic isolation<br />
Between channels and<br />
backplane bus<br />
yes<br />
Between channels and load<br />
voltage L+<br />
yes<br />
Between channels yes<br />
Between backplane bus<br />
and load voltage L+<br />
yes<br />
Permissible difference in potential (UISO) of signals<br />
from hazardous area<br />
Between channels and<br />
backplane bus<br />
Between channels and load<br />
voltage L+<br />
60 V DC<br />
30 V AC<br />
60 V DC<br />
30 V AC<br />
Between channels 60 V DC<br />
30 V AC<br />
Between backplane bus<br />
and load voltage L+<br />
60 V DC<br />
30 V AC<br />
Voltages, currents, potentials continued<br />
Permissible difference in potential (UISO) for signals<br />
from non-hazardous area<br />
Between channels and<br />
backplane bus<br />
Between channels and load<br />
voltage L+<br />
400 V DC<br />
250 V AC<br />
400 V DC<br />
250 V AC<br />
Between channels 400 V DC<br />
250 V AC<br />
Between backplane bus<br />
and load voltage L+<br />
Insulation tested<br />
Channels with respect to<br />
backplane bus and load<br />
voltage L+<br />
Channels among each<br />
other<br />
Between load voltage L+<br />
and backplane bus<br />
Current input<br />
From backplane bus<br />
From load voltage L+<br />
(at rated data)<br />
75 V DC<br />
60 V AC<br />
with 1500 V AC<br />
with 1500 V AC<br />
with 500 V DC<br />
max. 70 mA<br />
max. 160 mA<br />
Module power loss typical 3 W<br />
Status, interrupts, diagnostics<br />
Status indication<br />
Outputs green LED per channel<br />
Interrupts<br />
Diagnostic interrupt configurable<br />
Diagnostic functions<br />
Group fault indication red LED (SF)<br />
Channel fault indication red LED (F)<br />
per channel<br />
Diagnostic functions<br />
readout<br />
possible<br />
Monitoring for<br />
Short-circuit I 20.5 mA (10%)<br />
Wire break I 0.15 mA<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04