SIMATIC S7 Ex Digital Modules<br />

Digital output SM 322; DO 4 x 15V/20mA<br />

Dimensions and Weight<br />

Dimensions W x H x D (mm) 40 x 125 x 120<br />

Weight approx. 230 g<br />

Module-specific data<br />

Number of outputs 4<br />

Line length, shielded max. 200 m<br />

Type of protection PTB<br />

(see Appendix A)<br />

2-26<br />

[EEx ib] <strong>II</strong>C<br />

to EN 50020<br />

Test number Ex-96.D.2102 X<br />

Type of protection FM<br />

(see Appendix B)<br />

Voltages, currents, potentials<br />

Bus power supply<br />

Rated load voltage L+<br />

Reverse voltage protection<br />

Total current of outputs<br />

Horizontal arrangement up<br />

to 60 C<br />

Vertical arrangement up to<br />

40 C<br />

CL I, DIV 2,<br />

GP A, B, C, D T4<br />

5 V DC<br />

24 V DC<br />

yes<br />

No restrictions<br />

No restrictions<br />

Galvanic isolation<br />

Between channels and<br />

backplane bus<br />

yes<br />

Between channels and load<br />

voltage L+<br />

yes<br />

Between channels yes<br />

Between backplane bus<br />

and load voltage L+<br />

yes<br />

Permissible difference in potential (UISO) of signals<br />

from hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and load<br />

voltage L+<br />

60 V DC<br />

30 V AC<br />

60 V DC<br />

30 V AC<br />

Between channels 60 V DC<br />

30 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

60 V DC<br />

30 V AC<br />

Voltages, currents, potentials continued<br />

Permissible difference in potential (UISO) for signals<br />

from non-hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and load<br />

voltage L+<br />

400 V DC<br />

250 V AC<br />

400 V DC<br />

250 V AC<br />

Between channels 400 V DC<br />

250 V AC<br />

Between backplane bus<br />

and load voltage L+<br />

Insulation tested<br />

Channels with respect to<br />

backplane bus and load<br />

voltage L+<br />

Channels among each<br />

other<br />

Between load voltage L+<br />

and backplane bus<br />

Current input<br />

From backplane bus<br />

From load voltage L+<br />

(at rated data)<br />

75 V DC<br />

60 V AC<br />

with 1500 V AC<br />

with 1500 V AC<br />

with 500 V DC<br />

max. 70 mA<br />

max. 160 mA<br />

Module power loss typical 3 W<br />

Status, interrupts, diagnostics<br />

Status indication<br />

Outputs green LED per channel<br />

Interrupts<br />

Diagnostic interrupt configurable<br />

Diagnostic functions<br />

Group fault indication red LED (SF)<br />

Channel fault indication red LED (F)<br />

per channel<br />

Diagnostic functions<br />

readout<br />

possible<br />

Monitoring for<br />

Short-circuit I 20.5 mA (10%)<br />

Wire break I 0.15 mA<br />

I/O Modules with Intrinsically-Safe Signals<br />