SIMATIC S7 HART Analog Modules<br />
4.8.5 Additional Parameter Data Records<br />
Structure of the<br />
parameter data<br />
records 128 and<br />
129<br />
Notes on the<br />
additional<br />
parameters<br />
4-36<br />
The following figure shows the structure of the additional parameter data<br />
records 128 for channel 0 and 129 for channel 1. The settings affect the<br />
assigned channel.<br />
Byte 0<br />
Byte 1<br />
Byte 2<br />
7 6 5 4 3 2 1 0<br />
Number of repeated attempts<br />
during HART communication<br />
Wire break filter time,<br />
unit: 0.25 seconds (AI HART)<br />
Time required to update<br />
HART variables in user data<br />
area, see Figure 4-20<br />
Unit: 1/4 second<br />
Fig. 4-19 Parameter data records 128 and 129 of the HART analog modules<br />
The additional parameters comprise parameters which you do not normally<br />
need to change, as they have already been set to a optimized value: the<br />
following table provides explanations of the parameters and the default<br />
values.<br />
Table 4-15 Additional parameters of the HART analog module<br />
Parameter Explanation Value range and default setting<br />
Repeated<br />
attempts<br />
Wire break<br />
filter time 1)<br />
If the HART analog modules transmit a command to<br />
the field device and the connection is busy, the set<br />
number of repeated attempts is started.<br />
A wire break is only signaled if it occurs for longer than<br />
the set filter time.<br />
Update time The HART modules send the HART command 1<br />
automatically, to read the present value of the primary<br />
variable.<br />
Value range: 0 to 255,<br />
Default setting: 3,<br />
No repeat attempts: 0<br />
Value range: 0 to 20,<br />
Default setting: 3 0.75 seconds,<br />
No filter time: 0<br />
Value range: 0 to 255,<br />
Default setting: 12 3 seconds,<br />
No waiting time: 0<br />
1) As some measuring transducers take longer than others to start up, you may find that several diagnostic interrupts<br />
are triggered during startup. The wire break filter time was introduced to avoid this problem.<br />
Default parameter<br />
assignment for DP<br />
master class 2<br />
When the HART analog modules have no parameters, for example, after a<br />
power failure, they can obtain default parameters from PROFIBUS-DP<br />
master class 2 while the programmable logic controller is deactivated. This is<br />
done with the aid of parameter data record No. 250 which consists of one<br />
byte with the value unequal 0. However, the assignment of default<br />
parameters can only be initiated when the module is in an unparameterized<br />
state. You can determine the state of the module by reading the diagnostic<br />
data record: see Figure 4-12.<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04