SIMATIC S7 HART Analog Modules<br />

4.8.5 Additional Parameter Data Records<br />

Structure of the<br />

parameter data<br />

records 128 and<br />

129<br />

Notes on the<br />

additional<br />

parameters<br />

4-36<br />

The following figure shows the structure of the additional parameter data<br />

records 128 for channel 0 and 129 for channel 1. The settings affect the<br />

assigned channel.<br />

Byte 0<br />

Byte 1<br />

Byte 2<br />

7 6 5 4 3 2 1 0<br />

Number of repeated attempts<br />

during HART communication<br />

Wire break filter time,<br />

unit: 0.25 seconds (AI HART)<br />

Time required to update<br />

HART variables in user data<br />

area, see Figure 4-20<br />

Unit: 1/4 second<br />

Fig. 4-19 Parameter data records 128 and 129 of the HART analog modules<br />

The additional parameters comprise parameters which you do not normally<br />

need to change, as they have already been set to a optimized value: the<br />

following table provides explanations of the parameters and the default<br />

values.<br />

Table 4-15 Additional parameters of the HART analog module<br />

Parameter Explanation Value range and default setting<br />

Repeated<br />

attempts<br />

Wire break<br />

filter time 1)<br />

If the HART analog modules transmit a command to<br />

the field device and the connection is busy, the set<br />

number of repeated attempts is started.<br />

A wire break is only signaled if it occurs for longer than<br />

the set filter time.<br />

Update time The HART modules send the HART command 1<br />

automatically, to read the present value of the primary<br />

variable.<br />

Value range: 0 to 255,<br />

Default setting: 3,<br />

No repeat attempts: 0<br />

Value range: 0 to 20,<br />

Default setting: 3 0.75 seconds,<br />

No filter time: 0<br />

Value range: 0 to 255,<br />

Default setting: 12 3 seconds,<br />

No waiting time: 0<br />

1) As some measuring transducers take longer than others to start up, you may find that several diagnostic interrupts<br />

are triggered during startup. The wire break filter time was introduced to avoid this problem.<br />

Default parameter<br />

assignment for DP<br />

master class 2<br />

When the HART analog modules have no parameters, for example, after a<br />

power failure, they can obtain default parameters from PROFIBUS-DP<br />

master class 2 while the programmable logic controller is deactivated. This is<br />

done with the aid of parameter data record No. 250 which consists of one<br />

byte with the value unequal 0. However, the assignment of default<br />

parameters can only be initiated when the module is in an unparameterized<br />

state. You can determine the state of the module by reading the diagnostic<br />

data record: see Figure 4-12.<br />

I/O Modules with Intrinsically-Safe Signals<br />