22.07.2013 Views

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1.6 Equipotential Bonding in Systems with Explosion Protection<br />

Equipotential<br />

bonding in a<br />

building<br />

Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Differences in potential can develop between the elements of electrical<br />

apparatus, connected with PE conductors, and conductive structural<br />

elements, piping etc. which does not pertain to the electrical apparatus. When<br />

implementing measures to bridge these differences in potential, sparks<br />

capable of causing ignition can be produced. To equalize the potentials,<br />

conductive metal parts which are accessible and can be touched must be<br />

connected to each other and to the PE conductor. Equipotential bonding with<br />

the PE conductor can be best implemented at the distribution board. The<br />

cross section of the bonding conductor must be at least that of the PE<br />

conductor. In all other cases, the equipotential bonding conductor must have<br />

a cross section of at least 10 mm2 of copper.<br />

The Ex modules feature metallic isolation between the backplane bus and the<br />

I/O circuit; there is therefore no need for connection to the equipotential<br />

bonding conductor. An exception is when a connection to the EB conductor<br />

must be made for measurement purposes. Where lightning protection devices<br />

are required in the intrinsically safe circuit (Section 1.9), they must be<br />

connected to the EB conductor at the same point as the shield of the<br />

intrinsically safe circuits.<br />

Generally, the measures described in DIN VDE 0165 (Table 1-1) should be<br />

implemented or complied with.<br />

Cable racks must be incorporated throughout the earthing system.<br />

In accordance with VDE 0100, Part 410 and Part 540 and DIN VDE 0185,<br />

equipotential bonding must be provided in every building and via the overall<br />

cabling of the automation system; if this is not the case, it must be installed.<br />

1-13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!