Structure of the<br />

diagnostic data<br />

record 130<br />

Structure of the<br />

diagnostic data<br />

records 131 and<br />

151<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The following figure shows the structure of the diagnostic data record 130,<br />

which you can request to implement automatic recognition of the connected<br />

HART measuring transducer or the HART signal control elements.<br />

Bytes 1/0 for<br />

channel 0<br />

and bytes 5/4<br />

for channel 1<br />

Bytes 3/2 for<br />

channel 0<br />

and<br />

bytes 7/6<br />

for channel 1<br />

15 8 7<br />

0 Bit no.<br />

Bits 1 to 15 = 0<br />

1 = HART field device<br />

found<br />

0 = no HART field device<br />

connected<br />

15 8 7<br />

0 Bit no.<br />

Bits 1 to 15 = 0 1 = HART identification<br />

found<br />

0 = no HART<br />

identification present<br />

Fig. 4-17 Diagnostic data record 130 of the HART analog modules<br />

These contain the data corresponding to the identifiers marked in data record<br />

130: the address of the HART field device which was found and the HART<br />

identification with tags or identifiers for a signal control element. The<br />

structure is illustrated in the following figure.<br />

Data record 131 for channel 0 (length: 38 bytes)<br />

Data record 151 for channel 1 (length: 38 bytes)<br />

Byte 0<br />

Byte 1<br />

Byte 16<br />

Byte 17<br />

Byte 37<br />

7 6 5 4 3 2 1 0<br />

.<br />

.<br />

.<br />

.<br />

SIMATIC S7 HART Analog Modules<br />

No. of bytes for the response<br />

data to the HART command 0<br />

HART identification:<br />

response data to the HART<br />

command 0<br />

(“long-frame” address: bytes1,2<br />

and 9-11 )<br />

Measuring point identifiers<br />

(“tags”):<br />

Response data to the HART<br />

command 13<br />

Fig. 4-18 Diagnostic data records 131 and 151 of the HART analog module<br />

4-35