SIMATIC S7 HART Analog Modules<br />

Access to the field<br />

devices<br />

Modifying the<br />

parameters of the<br />

field devices<br />

Information on<br />

status<br />

4-10<br />

The HART analog module generally accepts the modification of parameters<br />

for the field devices. Access rights can only be allocated using the parameter<br />

assignment tool.<br />

To modify the parameters of the field devices connected to the HART analog<br />

modules, proceed as follows:<br />

Steps<br />

1<br />

2<br />

3<br />

To modify the parameters of a field device,<br />

enter a HART command using the SIMATIC<br />

PDM parameter assignment tool.<br />

When the parameters of the field device<br />

are modified, the HART analog module<br />

triggers a diagnostic interrupt, provided<br />

this option is enabled.<br />

This diagnostic interrupt must be<br />

acknowledged by the programmable logic<br />

controller at the end of the block OB82 before<br />

you can access the field device again: the<br />

acknowledgement is generally made from the<br />

programmable logic controller.<br />

Fig. 4-7 How to modify the parameters of the field devices<br />

SIMATIC<br />

PDM<br />

STEP7<br />

After you have modified the parameters of a HART field device, the<br />

corresponding bit is entered in the device status. This should be regarded as<br />

an indicator and not as an error and is reset by the module. For more<br />

information, see HART status bytes Section 4.5.1. You have to acknowledge<br />

the automation system diagnostic interrupt (OB 82) before you can have<br />

access to the field device again.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04