Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

1.7.2 Wiring and Cabling in Cable Bedding Made of Metal or in Conduits<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Cable bedding made of metal must be incorporated in the protective<br />

measures to counteract indirect contact. This can be achieved by routing an<br />

existing ground conductor made of steel strip or with a good conductive<br />

connection between individual beds.<br />

For single laying, conduits made of metal are now only usually used where<br />

particular mechanical or thermal stress is developed. In general, PVC<br />

conduits of two different types are used depending on the expected<br />

mechanical stress. Remember, however, that PVC exhibits a linear expansion<br />

which is about 8 times of that of metal. The fixing points must therefore be<br />

such that the linear expansion is taken up.<br />

1.7.3 Summary of Requirements of DIN VDE 0165/02.91<br />

Table 1-1 Contents of DIN VDE 0165/02.91<br />

The following table provides, once again, an overview of the most important<br />

stipulations of DIN VDE 165/02.91 for cables and lines.<br />

Application Requirements of cables and lines<br />

General requirements:<br />

Observe additional requirement for ”i”<br />

and zone 0<br />

(smaller cross section permissible for<br />

multicore lines with more than 5 cores,<br />

and lines for measurement and control,<br />

for example)<br />

Permissible types for portable/mobile<br />

apparatus (does not apply to<br />

intrinsically safe systems)<br />

Select according to mechanical, chemical and<br />

thermal influences<br />

(refer to DIN VDE 0298 and DIN VDE 0891)<br />

Protect against fire spread (e.g. lay cables in sand;<br />

verify burning characteristics of lines in accordance<br />

with VDE0472 Part 804, test type B)<br />

Copper or aluminum conductor material (Al only for<br />

multicore cables from 25 mm2 or single-core cables from<br />

35 mm2 ; use suitable connection elements)<br />

Minimum cross sections for copper conductor:<br />

Single-core cable: 1 mm fine,<br />

1.5 mm solid conductor<br />

Multicore cable: 0.75 mm fine, otherwise as above<br />