Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

1.1 Fundamental Guidelines and Specifications<br />

Approval<br />

FM approval<br />

Safety Extra-Low<br />

Voltage<br />

1-2<br />

Note<br />

Ex systems may only be installed by authorized personnel!<br />

SIMATIC S7 Ex modules have [EEx ib] <strong>II</strong>C approval. This means they are<br />

classified as associated apparatus and must therefore be installed outside<br />

hazardous areas. Intrinsically safe electrical apparatus for Zone 1 and 2 may<br />

be connected. The approval applies to all explosive gas mixtures of Groups<br />

<strong>II</strong>A..<strong>II</strong>C (see Manual: “Principles of Intrinsically-Safe Design“, Chapter<br />

“Secondary Explosion Protection”, “Marking of Explosion- Protected<br />

Electrical Apparatus” and The Intrinsic Safety ”i” Type of Protection“)<br />

Refer to the Certificates of Conformity (Appendix A) for the safety-relevant<br />

limits. In Appendix A you will also find explanations of the designations<br />

used.<br />

SIMATIC S7 Ex modules feature the following FM approvals (see Manual:<br />

“Principles of Intrinsically-Safe Design“, Chapter “Regulations for<br />

Explosion Protection Outside the CENELEC Member States”) :<br />

FM CL I, DIV 2, GP A, B, C, D, T4<br />

In compliance with these approvals, the modules can be used in areas which<br />

contain volatile flammable liquids or flammable gasses which are normally<br />

within closed vessels or systems, from which they can only escape under<br />

abnormal operating or fault conditions. The approval applies to all test gasses.<br />

A surface temperature no higher than 135 C (T4) occurs at ambient<br />

temperatures of 60 C.<br />

SIMATIC S7 Ex modules must be operated with a ”safety functional<br />

extra-low voltage”. This means that only a voltage of U 60 V must be<br />

applied to the modules even in the event of a fault.You will find more<br />

detailed information on the safety extra-low voltage in the specifications for<br />

the power supplies to be used.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04