SIMATIC S7 Ex Analog Modules<br />

Temperature<br />

range, climatic,<br />

Pt 100, Pt 200<br />

3-8<br />

Table 3-7 shows the representation of the digitized measured value for the<br />

climatic temperature range of the sensor Pt 100, Pt 200 in accordance with<br />

DIN 43760 and DIN IEC 751.<br />

Table 3-7 Representation of the digitized measured value of an analog input<br />

module (temperature range, climatic, Pt 100, Pt 200)<br />

Temperature range,<br />

climatic<br />

Pt 100, Pt 200<br />

in C<br />

Decimal Hexadecimal Range<br />

> 325.12 32767 7FFFH Overflow<br />

325.12<br />

:<br />

276.49<br />

276.48<br />

:<br />

-200.00<br />

-200.01<br />

:<br />

-240.00<br />

32512<br />

:<br />

27649<br />

27648<br />

:<br />

-20000<br />

-20001<br />

:<br />

-24000<br />

7F00H<br />

:<br />

6C01H<br />

6C00H<br />

:<br />

B1E0<br />

B1E1<br />

:<br />

A240H<br />

Overrange 1)<br />

Rated range<br />

Underrange 2)<br />

< - 240.00 -32768 8000H Underflow<br />

1) The same degree of accuracy as in the rated range is guaranteed in the overrange Pt<br />

100, Pt 200 climatic.<br />

2) The characteristic of the Pt 100, Pt 200 sensor is not defined in the underrange. The<br />

rise of the characteristic curve is retained on leaving the linearized rated range. It is<br />

not possible to specify the accuracy of these ranges.<br />