Temperature<br />

range, standard,<br />

Pt 100, Pt 200<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 3-6 shows the representation of the digitized measured value for the<br />

standard temperature range of the sensor Pt 100, Pt 200 in accordance with<br />

DIN 43760 and IEC 751.<br />

Table 3-6 Representation of the digitized measured value of an analog input<br />

module (temperature range, standard; Pt 100, Pt 200)<br />

Temperature range,<br />

standard 850 C<br />

Pt 100, Pt 200<br />

in C<br />

Decimal Hexadecimal Range<br />

> 1300.0 32767 7FFFH Overflow<br />

1300.0<br />

:<br />

850.1<br />

850.0<br />

:<br />

-200.0<br />

-200.1<br />

:<br />

-240.0<br />

13000<br />

:<br />

8501<br />

8500<br />

:<br />

-2000<br />

-2001<br />

:<br />

-2400<br />

SIMATIC S7 Ex Analog Modules<br />

32C8H<br />

:<br />

2135H<br />

2134H<br />

:<br />

F830H<br />

F82FH<br />

:<br />

F6A0H<br />

Overrange 1)<br />

Rated range<br />

Underrange 2)<br />

< -240.0 -32768 8000H Underflow<br />

1) The characteristic of the Pt 100, Pt 200 sensor is not defined in the overrange. The<br />

overrange has been extended to 1300 C in order to be able to incorporate future<br />

technical developments of platinum thermal resistors (thermistors). It is not possible<br />

to specify the accuracy of this range.<br />

2) The characteristic of the Pt 100, Pt 200 sensor is not defined in the underrange. The<br />

rise of the characteristic curve is retained on leaving the linearized rated range. It is<br />

not possible to specify the accuracy of this range.<br />