Temperature range<br />

type L<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Table 3-14 shows the representation of the digitized measured value for the<br />

temperature range, sensor type L.<br />

Table 3-14 Representation of the digitized measured value of an analog input<br />

module (temperature range, type L)<br />

Temperature<br />

range in C<br />

SIMATIC S7 Ex Analog Modules<br />

Decimal Hexadecimal Range<br />

> 1150.0 32767 7FFFH Overflow<br />

1150.0<br />

13500 2CECH<br />

:<br />

:<br />

:<br />

Overrange<br />

900.1<br />

9001 2329H<br />

1)<br />

900.0<br />

9000 2328H<br />

:<br />

:<br />

:<br />

:<br />

:<br />

:<br />

Rated range<br />

-200.0<br />

-2000 F830H<br />

-200.1 -2001 F82FH Underrange 1)<br />

In the case of incorrect wiring (e.g. polarity reversal, open inputs) or a sensor fault in<br />

the negative range (e.g. incorrect type of thermocouple), on dropping below F380H the<br />

analog input module signals underflow and outputs 8000H .<br />

1) The characteristic of the thermocouple is not defined in the overrange and<br />

underrange. The rise of the characteristic curve is retained on leaving the linearized<br />

rated range. It is not possible to specify the accuracy of these ranges.<br />