SIMATIC S7 Ex Digital Modules<br />

2.3 Digital Output Module SM 322; DO 4 x 15V/20mA<br />

Order number<br />

Characteristics<br />

Wiring diagram<br />

Notes on<br />

intrinsically-safe<br />

installation<br />

Power supply for a<br />

intrinsically-safe<br />

structure<br />

2-24<br />

6ES7 322-5RD00-0AB0<br />

Refer to the description of the digital output module SM 322;<br />

DO 4 x 24V/10mA (see Section 2.2) for the module characteristics.<br />

Fig. 2-5 shows the terminal diagram of SM 322; DO 4 x 15V/20mA.<br />

SM 322<br />

DO 4 x 15VDC/20mA<br />

Output 0<br />

Output 1<br />

Output 2<br />

Output 3<br />

X 2<br />

3 4<br />

322-5RD00-0AB0<br />

SF<br />

F0<br />

0<br />

F1<br />

1<br />

x x<br />

[EEx ib] <strong>II</strong>C<br />

F2<br />

2<br />

F3<br />

3<br />

1<br />

L+<br />

2<br />

3<br />

4 CH 0<br />

5<br />

6<br />

7<br />

8 CH 1<br />

9<br />

10<br />

11<br />

12<br />

13 CH 2<br />

14<br />

15<br />

16<br />

17 CH 3<br />

18<br />

19<br />

20<br />

M<br />

Channel number Terminal diagram<br />

SF group fault [red] F (0...3) channel-specific fault<br />

indication [red]<br />

0...3 status indication [green]<br />

Fig. 2-5 Wiring diagram of SM 322; DO 4 x 15V/20mA<br />

You must connect the DM 370 dummy module between the CPU or IM 153-2<br />

(distributed configuration) and the Ex I/O modules whose signal cables lead into<br />

the hazardous area. In a distributed configuration with an active backplane bus,<br />

you should use the explosion-proof partition instead of the dummy module.<br />

Additional information on system design can be found in Sections 1.3 - 1.5.<br />

In order to maintain the dearances and creepage distances, L+ / M must be<br />

routed via the line chamber LK393 when operating modules with signal<br />

cables that lead to the hazardous location, see Section 1.2.<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04