Modifying the<br />

parameters of the<br />

field devices<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Remember that the field devices signal each change in the parameters as a<br />

configuration change to the HART analog module. This leads to a diagnostic<br />

interrupt on the programmable controller, provided this option is enabled. It<br />

is advisable to disable the diagnostic interrupt during configuration and<br />

parameter assignment. You can do this when you assign parameters to the<br />

HART analog module, see Section 4.4.<br />

4.3.2 Operating Phase of HART Analog Module and Field Devices<br />

Operating phase<br />

In the operating phase you must distinguish between the cyclic return of user<br />

data, acyclic HART interventions, and cyclic HART communication.<br />

The cyclic user data, for example measured values, are obtained from the<br />

programmable logic controller (PROFIBUS DP master class 1): The user<br />

data area exists for this purpose. In the case of the HART analog input<br />

module, this is the input area; in the case of the HART analog output<br />

module, it is the output area.<br />

Acyclic intervention for diagnostics and modifying the parameters of the<br />

field devices is carried out with the SIMATIC PDM parameter assignment<br />

tool (on PROFIBUS DP master class 2) or with a HART hand-held device<br />

using HART commands and HART responses.<br />

You can establish cyclic HART communication by writing / reading a<br />

data record in conjunction with the data ready ID.<br />

Steps<br />

1<br />

2<br />

3<br />

Fig. 4-6 The operating phase<br />

Switch the programmable logic controller to<br />

“RUN”: user data are transmitted cyclically via<br />

PROFIBUS DP.<br />

You can evaluate the user data cyclically<br />

in your user program.<br />

SIMATIC S7 HART Analog Modules<br />

You can use the SIMATIC PDM parameter<br />

assignment tool for diagnostic purposes and<br />

modify the parameters of the field devices:<br />

Start by double-clicking channel 0 (line 2) or<br />

channel 1 (line 3) of the HART analog module,<br />

depending on where the particular field device<br />

is connected.<br />

STEP7<br />

SIMATIC<br />

PDM<br />

4-9