SIMATIC S7 Ex Analog Modules<br />

Parameterization<br />

Default setting<br />

Channel groups<br />

Non-connected<br />

output channels<br />

3-70<br />

The functions of the analog output module SM 332; AO 4 x 0/4...20 mA are<br />

set<br />

with STEP 7 (refer to /231/) or<br />

in the user program with SFCs (refer to /235/).<br />

The analog output module features default settings for type of output,<br />

diagnostics, interrupts etc. (see Table 3-23).<br />

These default settings are valid if re-parameterization has not been carried<br />

out via STEP 7.<br />

Table 3-37 shows the allocation of the 4 channels to the 4 channel groups of<br />

SM 332; AO 4 x 0/4...20 mA.<br />

Table 3-37 Allocation of 4 channels to 4 channel groups of<br />

SM 332; AO 4 x 0/4...20 mA<br />

Channel Allocated channel group<br />

Channel 0 Channel group 0<br />

Channel 1 Channel group 1<br />

Channel 2 Channel group 2<br />

Channel 3 Channel group 3<br />

Non-connected output channels of the analog output module SM 332;<br />

AO 4 x 0/4...20 mA must be deactivated to ensure no power is applied to<br />

them. You can deactivate an output channel with STEP 7 via the ”output”<br />

parameter block (see Section 3.6.3).<br />

I/O Modules with Intrinsically-Safe Signals<br />